PAGE 11
Aquavar IPC Start-Up Genie
CentriPro
Perform No Flow Power Calibration
Select Quick Menu
Select 04 Startup Genie
Change Setup Selection to Pump
Protection.
PERFORMING THE NO FLOW POWER CALIBRATION:
Select Enable for sleep mode.
Select 30 Hz for Sleep Frequency,
3 Seconds for Sleep Delay.