Why does the Xylem Controller show over voltage on the DC bus (Fault code 6)?
- SStephanie LewisAug 20, 2025
The over voltage fault on the DC bus is triggered by excessive regenerative energy being transferred from the load back to the drive. If this occurs when stopping or during deceleration, increase the deceleration ramp time using parameter P1-04:Deceleration ramp time.