Torque values
Control terminal
Torque value 0.8 Nm (7.00 lb in)
Power terminal
Drive size Nm lb in
2 1.0 8.85
3 1.0 8.85
4 4.0 3.00
5 15.0 11.10
6 20.0 15.00
Optional modules
Torque value 0.5 Nm (4.50 lb in)
Install the system
Requirements
The mechanical installation of pumps, switch, and sensors is completed.
The pumps that are installed must be equipped with FLS, thermal contacts. If no FLS is
used the P1-22:Leakage alarm setup parameter must be set to 0: Off.
The pumps must be installed with screened cables.
Do not install any type of automatic switchgear between the drive and the motor.
Install a two pump system
WS008323
1 2
1. Prepare the drives cable throughlet.
Electrical Installation
SRC 311 - SmartRun
Installation, Operation, and Maintenance Manual 21