No. Display message Description of display messages Corrective action
20 U-dEF User parameter defaults Displayed when the Up, Down, and Stop buttons are pressed
simultaneously.
Press the Off button to proceed.
22 FAn-F Cooling fan fault Check and if necessary, replace the internal cooling fan.
23 0–hEAt Ambient temperature too high The measured temperature around the drive is above the operating
limit.
Ensure that the drive internal cooling fan operates.
Ensure that the required space around the drive is observed,
and that the cooling airflow path is not restricted.
Increase the cooling airflow to the drive.
Reduce the load on the motor or drive.
24 0–tor9 Over-current error Current monitoring function has detected that the current levels are
above the normal operating condition for the application.
Check that mechanical load has not changed and that the load
is not jammed or stalled.
For pump applications, check for potential pump blockage.
25 U-tor9 Under-current error Current monitoring function has detected that the current levels are
below the normal operating condition for the application.
Check for mechanical breakages causing loss of load.
Check that the motor has not become disconnected from the
drive.
26 Out-F Drive output fault If the fault remains, then contact your sales and service
representative.
40 AtF–01 Autotune failed Measured motor stator resistance varies between phases.
Ensure that the motor is correctly connected and free from
faults.
Check the windings for correct resistance and balance.
41 AtF–02 Autotune failed Measured motor stator resistance is too large.
Ensure that the motor is correctly connected and free from
faults.
Check that the power rating corresponds to the power rating of
the connected drive.
42 AtF–03 Autotune failed Measured motor inductance is too low.
Ensure that the motor is correctly connected and free from
faults.
43 AtF–04 Autotune failed Measured motor inductance is too large.
Ensure that the motor is correctly connected and free from
faults.
Check that the power rating corresponds to the power rating of
the connected drive.
44 AtF–05 Autotune failed Measured motor parameters are not convergent.
Ensure that the motor is correctly connected and free from
faults.
Check that the power rating corresponds to the power rating of
the connected drive.
50 Sc-F01 Modbus communication error
detected
A valid Modbus telegram has not been received within the
watchdog time limit that is set in P5-05:Comms loss timeout.
Check that the network master or PLC still operates.
Check the connection cables.
Increase the value of P5-05:Comms loss timeout to a suitable
level.
Troubleshooting
SRC 311 - SmartRun
Installation, Operation, and Maintenance Manual 49