Aquavar IPC Start-Up Genie
CentriPro
AQUAVAR® INTELLIGENT PUMP CONTROLLER START-UP GENIE PARAMETERS (IM287)
(cont.)
• Feedback:
• Control Feedback Sources: 20-00, 20-03, 20-06
• Feedback 1,2,3
Feedback Function: 20-20
• Low Feedback Value: 20-13
• High Feedback Value: 20-14
• Feedback Sensor Fault: 6-17
• Setpoint:
• Number of Setpoints: 5-15, 20-21, 20-22
• Flow Compensation: 22-80:
• Is the speed at the design point Know?: 22-82
• Square-linear Curve Approximation: 22-81
• Speed at Design Point (Hz): 22-86
• Speed at No-Flow (Hz): 22-84
• Pressure at No-Flow Speed: 22-87
• Pump Protection
• Sleep Mode: 22-22, 22-23, Smart Logic (13-10.1)
• Sleep Frequency: 4-12
• Sleep Delay: 22-24
• Restart Difference: 22-44
• Minimum Run Time: 22-40
• Minimum Sleep Time: 22-41
• Flow Check Window:
• Flow Check Low Time: Smart Logic (13-20.1)
• Flow Check High Time: Smart Logic (13-20.0)
• Run the No Flow Power Calibration Setup: 22-20
• No Water/Loss of Prime: 22-21
• No Water/Loss of Prime Limit: 22-39
• No Water/Loss of Prime Restart: 22-26
• No Water/Loss of Prime Protection Delay: 22-27
• Under Pressure Function: 22-50
• Under Pressure Delay Time: 22-51
• Under Pressure Difference: 22-52
• Setup Protection Through Digital Input 19: 5-11
• Setup Pump Protection Trough Digital Input 27:
5-12
• Pump Protect Delay: 22-00
• Digital Input
• Terminal 19 Digital Input: 5-11
• Terminal 27 Digital Input: 5-12
• Terminal 29 Digital Input: 5-13
• Terminal 32 Digital Input: 5-14
• Terminal 33 Digital Input: 5-15
• Relay & Analog Output
• Relay Function:
Relay 1: 5-40.0
Relay 2: 5-40.1
Relay On Delay 1: 5-41.0
Relay On Delay 2: 5-41.1
Terminal 42 Output: 6-50
Terminal 42 Output Min: 6-51
Terminal 42 Output Max: 6-52
• Communication Setup
Protocol: 8-30 (Modbus RTU, FC MC, FC,
Metasys N2)
Address: 8-31
Baud Rate: 8-32
Parity/Stop Bits: 8-33
Minimum Response Delay: 8-35
Maximum Response Delay: 8-36
Maximum Inter-Char Delay: 8-37
Estimated cycle time: 8-34
Protocol: 8-30 (FLN)
– Control Timeout Time: 8-03
– Control Timeout Function: 8-04
Protocol: 8-30, BACnet (8-7*)
– Coasting Select: 8-50
– BACnet Device Instance: 8-70
– MS/TP Max Master: 8-72
Copy to LCP: 0-50 set to “All to LCP”
Copy from LCP: 0-50 set to “All from LCP”