PAGE 8
Aquavar IPC Start-Up Genie
CentriPro
Select Yes to Autoset the rest of the settings.
For Simplex conguration, here are the
parameters that will get autoset:
Autoset Conguration
Constant
Pressure
Transducer Max Feedback 300 [unit]
Transducer Type 4-20mA
Feedback 1 Source AI 53
PID Performance Normal
Sleep Mode Enabled
Sleep Frequency 30 Hz
Restart Difference 5 [unit]
No Water/Loss of Prime Fault Enabled
No Water/Loss of Prime Restart Time 10 min.
Select Setpoint 1
Proceed with the down arrow on the next
two screens as you are verifying that your
Pressure Transducer is a 300 PSI, you are
wired in on Analog Input 53, that your
sleep frequency is 30 Hz, and your restart
difference is 5%, the No Water loss of prime
fault is enabled, and your restart time is 10
Minutes.
Cycle Power Off and prepare control wiring