3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 13
Wiring Specification
Main Circuit
Use the fuses and line filters listed in the table below when wiring the main circuit. Make sure not to exceed the given
tightening torque values.
Model
CIMR-A
EMC Filter
[Schaffner]
Main Fuse
[Bussmann]
Recom.
Motor cable
(mm
2
)
Main Circuit Terminal Sizes
R/L1,S/L2,T/L3,
U/T1,V/T2,W/T3,
– , +1, +2
+3 B1, B2
2A0004
<1> Connect two of the same filters in parallel. Refer to the Technical Manual for details.
FS5972-10-07
FWH-70B
2.5
M4
–
M4
M4
2A0006
2A0010
FS5972-18-07
2A0012
2A0021
FS5972-35-07
FWH-90B
2A0030 FWH-100B 6
M5
2A0040
FS5972-60-07
FWH-200B
10
2A0056
16
M6
M5 M6
2A0069
FS5972-100-35
M8
2A0081
FWH-300A
25
2A0110
FS5972-170-40
35 M8
M8
2A0138 FWH-350A 50
M10
M10
2A0169
FS5972-250-37 FWH-400A
70
M10 –
2A0211 95
2A0250
FS5972-410-99
FWH-600A
95 × 2P
M12 M12
2A0312 FWH-700A
2A0360
FS5972-600-99
FWH-800A 240
2A0415 FWH-1000A 300
4A0002
FS5972-10-07
FWH-40B
2.5
M4
–
M4
M4
4A0004 FWH-50B
4A0005
FWH-70B
4A0007
4A0009
FS5972-18-07 FWH-90B
4A0011
4A0018
FS5972-35-07
FWH-80B
M5
4A0023 FWH-100B 4
4A0031 FWH-125B
6M5
M5
M6
4A0038
FS5972-60-07
FWH-200B
4A0044
FWH-250A
16
M6
M8
4A0058
M8
M8
4A0072
FS5972-100-35 25
4A0088
M10
–
4A0103
FS5972-170-40
35
4A0139 FWH-350A 50
M10 M10
4A0165 FWH-400A 70
4A0208 FS5972-250-37 FWH-500A 95
4A0250
FS5972-410-99
FWH-600A 120
4A0296 FWH-700A 185
M12 M12
4A0362 FWH-800A 240
4A0414
FS5972-600-99
FWH-800A 95 × 2P
M12
4A0515 FWH-1000A 150 × 2P
4A0675 FS5972-800-99 FWH-1200A 95 × 4P
4A0930 FS5972-600-99 <1> FWH-1200A 120 × 4P
4A1200 FS5972-800-99 <1> FWH-1600A (95 × 4P) × 2