EasyManua.ls Logo

YASKAWA GA50C4004ABA - Page 113

YASKAWA GA50C4004ABA
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation
3
3.15 Protect the Drive during Failures
YASKAWA SIEPC71061753C GA500 Technical Manual 113
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND HD
Class J, CC, and T Fuse
Rated Current
A
Model
Fuse Rated Current
A
2042 11 (15) 7.5 (10) 70 FWH-150B 150
2056 15 (20) 11 (15) 90 FWH-200B 200
2070 18.5 (25) 15 (20) 110 FWH-200B 200
2082 22 (30) 18.5 (25) 125 FWH-225A 225
Three-Phase 400 V Class
Table 3.18 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND HD
Class J, CC, and T Fuse
Rated Current
A
Model
Fuse Rated Current
A
4001 0.37 (1/2) 0.37 (1/2) 3 FWH-40B 40
4002 0.75 (1) 0.55 (3/4) 3.5 FWH-40B 40
4004 1.5 (2) 1.1 (2) 7 FWH-50B 50
4005 2.2 (3) 1.5 (3) 9 FWH-70B 70
4007 3.0 (4) 2.2 (3) 12 FWH-70B 70
4009 4.0 (5) 3.0 (4) 15 FWH-90B 90
4012 5.5 (7.5) 4.0 (5) 20 FWH-90B 90
4018 7.5 (10) 5.5 (10) 30 FWH-80B 80
4023 11.0 (15) 7.5 (10) 40 FWH-100B 100
4031 15.0 (20) 11.0 (15) 50 FWH-125B 125
4038 18.5 (25) 15.0 (20) 60 FWH-175B 175
4044 22.0 (30) 18.5 (25) 70 FWH-200B 200
4060 30.0 (40) 22.0 (30) 100 FWH-200B 200