EasyManua.ls Logo

YASKAWA GA50C4004ABA - F6: Communication Options

YASKAWA GA50C4004ABA
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.9 F: Options
386 YASKAWA SIEPC71061753C GA500 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F1-11
(038A)
Speed Deviation Detect
DelayTime
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in F1-10 to cause dEv [Speed Deviation].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
0.5 s
(0.0 - 10.0 s)
604
F1-14
(038D)
Encoder Open-Circuit
Detect Time
Sets the length of time that the drive must not receive a pulse signal to cause PGo
[Encoder (PG) Feedback Loss].
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent]
faults.
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
2.0 s
(0.0 - 10.0 s)
604
F6: Communication Options
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects bUS [Option Communication Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
610
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
610
F6-03
(03A4)
Comm External Fault
(EF0) Select
Sets the method to stop the motor or let the motor continue operating when the drive
detects EF0 [Option Card External Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
611
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install a CC-Link option (SI-C3) to the drive, the setting value changes
to 0.0 s.
2.0 s
(0.0 - 12.0 s)
611
F6-06
(03A7)
Torque Reference/Limit
by Comm
Sets the function that enables and disables the torque reference and torque limit
received from the communication option.
0 : Disabled
1 : Enabled
0
(0, 1)
611
F6-07
(03A8)
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed reference when the
freqency reference source is NetRef or ComRef (communication option card or
MEMOBUS/Modbus communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
1
(0, 1)
611
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized
with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
612
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set a node address that is different than all other node addresses. Do not
set this parameter to 0. Incorrect parameter settings will cause AEr [Station Address
Setting Error] errors and the L.ERR LED on the option will come on.
0
(0 - 64)
612
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA50C4004ABA

Related product manuals