EasyManua.ls Logo

YASKAWA GA50C4004ABA - Page 236

YASKAWA GA50C4004ABA
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3 MEMOBUS/Modbus Communications
236 YASKAWA SIEPC71061753C GA500 Technical Manual
Register No.
(Hex.)
Description
00AB
Drive rated current
Note:
The unit of display is different for different models.
B001 - B018, 2001 - 2042, and 4001 - 4023: 0.01 A
2056 - 2082, 4031 - 4060: 0.1 A
00AC
U1-05 [Motor Speed]
Units: min
-1
or r/min
Note:
Set E2-04, E4-04, E5-04, E9-08 [Motor Pole Count].
00AD
Units: 0.01%
00AE, 00AF Reserved
00B0
Option codes connected to
CN5
The drive stores option codes in the register.
SI-C3 = 5343 (Hex.)
SI-EM3 = 1005 (Hex.)
SI-EN3 = 1006 (Hex.)
SI-EP3 = 1007 (Hex.)
SI-ES3 = 1001 (Hex.)
SI-ET3 = 1004 (Hex.)
SI-N3 = 534E (Hex.)
SI-P3 = 5350 (Hex.)
SI-S3 = 5353 (Hex.)
SI-T3 = 5354 (Hex.)
00B1 - 00B4 Reserved
00B5
U1-16 [SFS Output
Frequency]
Units: min
-1
or r/min
Note:
Set E2-04, E4-04, E5-04, E9-08 [Motor Pole Count].
00B6
Units: 0.01%
00B7
Frequency reference
monitor
Units: min
-1
or r/min
Note:
Set E2-04, E4-04, E5-04, E9-08 [Motor Pole Count].
00B8
Units: 0.01%
00B9 - 00BE Reserved
00BF
Operation error number
xx of oPExx is displayed.
00C0
Fault Description 3
bit 0 Reserved
bit 1 Uv1 [DC Bus Undervoltage]
bit 2 Uv2 [Control Power Undervoltage]
bit 3 Uv3 [Soft Charge Answerback Fault]
bit 4 SC [Short Circuit/IGBT Failure]
bit 5 GF [Ground Fault]
bit 6 oC [Overcurrent]
bit 7 ov [Overvoltage]
bit 8 oH [Heatsink Overheat]
bit 9 oH1 [Heatsink Overheat]
bit A oL1 [Motor Overload]
bit B oL2 [Drive Overload]
bit C oL3 [Overtorque Detection 1]
bit D oL4 [Overtorque Detection 2]
bit E rr [Dynamic Braking Transistor Fault]
bit F rH [Braking Resistor Overheat]

Table of Contents

Other manuals for YASKAWA GA50C4004ABA

Related product manuals