12.9 L: Protection Functions
696 YASKAWA SIEPC71061753C GA500 Technical Manual
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
3 : Alarm Only
The keypad shows oH3 and the drive continues operation. The output terminal set for Alarm [H2-01 to H2-03 =
10] activates.
L1-04: Motor Thermistor oH Fault Select
No.
(Hex.)
Name Description
Default
(Range)
L1-04
(0483)
Motor Thermistor oH Fault
Select
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat
Fault (PTC Input)] detection level.
1
(0 - 2)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault [H2-01 to H2-03 =
E] activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
L1-05: Motor Thermistor Filter Time
No.
(Hex.)
Name Description
Default
(Range)
L1-05
(0484)
Motor Thermistor Filter
Time
Sets the primary delay time constant for the PTC input signal entered to the drive. This parameter
prevents accidental motor overheat faults.
0.20 s
(0.00 - 10.00 s)
L1-08: oL1 Current Level
No.
(Hex.)
Name Description
Default
(Range)
L1-08
(1103)
oL1 Current Level
Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0
A, you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10% to 150% of
the drive rated current)
When L1-08 = 0.0 A, the drive uses E2-01 [Motor Rated Current (FLA)] to detect the motor overload protection.
In PM control mode, the drive uses E5-03 [PM Motor Rated Current (FLA)] to detect the motor overload
protection.
When L1-08 0.0 A, the set value is the reference for motor overload protection.
Note:
Display is in these units:
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
0.1 A: 2056 to 2082, 4031 to 4060
When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.
L1-09: oL1 Current Level for Motor 2
No.
(Hex.)
Name Description
Default
(Range)
L1-09
(1104)
oL1 Current Level for
Motor 2
Sets the reference current for the motor 2 thermal overload detection. When the current level > 0.0
A, you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10 to150% of the
drive rated current)
When L1-09 = 0.0 A, the drive uses E4-01 [Motor 2 Rated Current] to detect the motor overload protection.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV