Specifications
5
5.1 Common Drive Specifications
YASKAWA TOEPC71061779E GA800 DRIVE INSTALLATION MANUAL
83
Item Specification
Speed Control Range
V/f: 1:40
CL-V/f: 1:40
OLV: 1:200
CLV: 1:1500
AOLV: 1:200
OLV/PM: 1:20
AOLV/PM: 1:100 (when high frequency injection is enabled)
CLV/PM: 1:1500
EZOLV: 1:100
Note:
Set n8-57 = 1 [HFI Overlap Selection = Enabled] for this Speed Control Range in AOLV/PM. When you use a non-Yaskawa PM motor, do Rotational
Auto-Tuning.
Speed control range of 1:100 for AOLV/PM is Instantaneous operation range. Correctly select the drive and motor capacity for continuous operation.
Zero Speed Control
Possible in these control methods:
CLV
AOLV/PM
CLV/PM
Torque Limits
Parameter settings allow different limits in four quadrants in these control methods:
OLV
CLV
AOLV
AOLV/PM
CLV/PM
EZOLV
Accel/Decel Time
0.0 s to 6000.0 s
The drive can set four pairs of different acceleration and deceleration times.
Braking Torque
Approximately 20%
Approximately 125% with a dynamic braking option
Short-time average deceleration torque
Motor output 0.4/0.75 kW: over 100%
Motor output 1.5 kW: over 50%
Motor output 2.2 kW and larger: over 20%, Overexcitation Braking/High Slip Braking allow for approximately 40%
Continuous regenerative torque: Approximately 20%. Dynamic braking option allows for approximately 125%, 10%ED, 10 s
WARNING
Set L3-04 = 0 [Stall Prevention during Decel = Disabled] when you operate the drive with:
a regenerative converter
regenerative unit
braking unit
braking resistor
braking resistor unit.
If you set the parameter incorrectly, the drive can decelerate for too long and cause serious injury or death.
Note:
Models 2004 to 2138 and 4002 to 4168 have a braking transistor.
Short-time average deceleration torque refers to the torque needed to decelerate the motor (uncoupled from the load) from the rated speed to zero. Motor
characteristics can change the actual specifications.
Motor characteristics change the continuous regenerative torque and short-time average deceleration torque for motors 2.2 kW and larger.
V/f Characteristics
Select from 15 pre-defined V/f patterns, or a user-set V/f pattern.
Main Control
Functions
Torque Control, Droop Control, Speed/Torque Control Switching, Feed Forward Control, Zero Servo Function, Restart After Momentary Power Loss, Speed
Search, Overtorque/Undertorque Detection, Torque Limit, 17 Step Speed (max.), Accel/Decel Switch, S-curve Acceleration/Deceleration, 3-wire Sequence,
Auto-Tuning (Rotational and Stationary), Dwell Function, Cooling Fan ON/OFF Switch, Slip Compensation, Torque Compensation, Frequency Jump, Upper/
Lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, Overexcitation Braking, High Slip Braking, PID Control (with Sleep
Function), Energy Saving Control, MEMOBUS/Modbus Communication (RS-485 max, 115.2 kbps), Auto Restart, Application Presets, DriveWorksEZ
(customized functions), Removable Terminal Block, Online Tuning, KEB, Overexcitation Deceleration, Inertia (ASR) Tuning, Overvoltage Suppression, High
Frequency Injection
*1 PM control methods are not available on 600 V models.
Table 5.2 Protection Functions
Item Specification
Motor Protection
Electronic thermal overload protection
Momentary
Overcurrent
Protection
Drive stops when the output current is more than 200% of the HD output current.