GPD315 Modbus RTU Technical Manual TM 4325
Page
7
Parameter n154 - Modbus Baud Rate
Parameter n154 selects the baud rate, as indicated by the following table:
Table 3.5 Modbus Baud Rate Selection
Parameter n154 Setting Baud Rate(bps)
0 2400
1 4800
2 9600
3 19200
The default setting of parameter n154 is ‘2’.
Parameter n155 - Modbus Parity Selection
Parameter n155 selects the parity, as indicated by the following table:
Table 3.6 Modbus Parity Selection
Parameter n155 Setting Parity Selection
0Even
1Odd
2 None
The default setting for parameter n155 is ‘2’.
Note:
It is necessary to recycle drive power for parameters n153 through n155 to take effect.