GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
23
Drive Parameter Registers (Read/Write)
Table 5-4 Drive Parameters
Parameter ADDR Name Set Description Default
0 N001 Can Be Read And Set; N002-N179 Others Read Only
1 N001-N039 Can Be Read And Set
2 N001-N067 Can Be Read And Set
3 N001-N113 Can Be Read And Set
4 N001-N179 Can Be Read And Set
5 Not Used
1
6 Clear Fault Record Only
7 Not Used
1
8 2-Wire Initialization (Parameters n180 – n210 re not initialized)
9 3-Wire Initialization (Parameters n180 – n210 re not initialized)
10 2-Wire Initialization (Us) (Parameters n180 – n210 re not initialized)
11 3-Wire Initialization (Us) (Parameters n180 – n210 re not initialized)
12 2-Wire Initialization (European)
4
13 3-Wire Initialization (European)
4
15 All Parameters Can Be Read And Set
n001 0101h
Password /
Initialization
20 Initialize All Parameters To Factory Defaults
1
0 V/F Control (initialized only by n001 set to 10 or 11)
n002 0102h
Control
Method
1 Open Loop Vector (initialized only by n001 set to 10 or 11)
0
0 Digital Operator
1 Terminal
2 Serial Communication
1
n003 0103h
Operation
Method
3OptionPCB
4
0 Digital Operator Pot
1 Frequency Reference 1 (N024)
2 Voltage Reference (0-10v)
3 Current Reference (4-20 Ma)
4 Current Reference (0-20 Ma)
5 Pulse Train Reference
6 Serial Communication (Address 002h)
2
n004 0104h
Reference
Selection
7OptionPCB
4
0RampToStop
n005 0105h Stop Method
1 Coast To Stop
0
0 Reverse Run Enabled
n006 0106h
Reverse
Prohibit
1 Reverse Run Disabled
0
0 Stop Key Enabled.
n007 0107h
Stop Key
Function
1 Stop Key Is Active Only When N003 Is Set From Digital Operator
0
0 Frequency Ref. From Digital Operator Pot
n008 0108h
Frequency
Reference
Selection Local
1 Frequency Ref. From N024
0
0 Enter Required To Accept
n009 0109h
Freq. Ref.
Enter Req.
1 Enter Not Required To Accept
0
0 Disabled
n010 010Ah
Operator
Connection
Detection
1 Enabled (Operator Connection Fault Detect)
0
n011 010Bh
Max. Output
Frequency
50.0 - 400.0Hz 60.0
n012 010Ch Max. Voltage
0.1 - 255.0 (230V Drive)
0.2 - 510.0 (460 V Drive)
230
460
n013 010Dh
Freq. @ Max.
Voltage
0.2 - 400.0Hz 60