GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
24
Table 5-4 Drive Parameters (continued)
Parameter ADDR Name Set
Description
Default
n014 010Eh
Mid. Output
Frequency
0.1 - 399.9hz 1.5
n015 010Fh
Voltage @
Mid. Frequency
0.1 - 255.0 (230v Drive)
0.2 - 510.0 (460 V Drive)
12.0
24.0
n016 0110h
Min. Output
Frequency
0.1 - 10.0hz 1.5
n017 0111h
Voltage @ Min.
Frequency
0.1 - 255.0 (230v Drive)
0.2 - 510.0 (460 V Drive)
12.0
24.0
00.1s
n018 0112h
Accel / Decel
Time Unit
1 0.01s
0
n019 0113h
Acceleration
Time 1
000.0 999.9 or 1000 6000 Seconds (n018 = 0)
00.00 99.99 or 100.0 600.0 Seconds (n018 = 1)
10.0
n020 0114h
Deceleration
Time 1
000.0 999.9 or 1000 6000 Seconds (n018 = 0)
00.00 99.99 or 100.0 600.0 Seconds (n018 = 1)
10.0
n021 0115h
Acceleration
Time 2
000.0 999.9 or 1000 6000 Seconds (n018 = 0)
00.00 99.99 or 100.0 600.0 Seconds (n018 = 1)
10.0
n022 0116h
Deceleration
Time 2
000.0 999.9 or 1000 6000 Seconds (n018 = 0)
00.00 99.99 or 100.0 600.0 Seconds (n018 = 1)
10.0
0NoS-Curve
1 0.2 Second
2 0.5 Second
n023 0117h
S-Curve
Selection
3 1.0 Second
0
n024 0118h
Frequency
Reference 1
0.00 - 9.99hz or 100.0 - 400.0hz 6.00
n025 0119h
Frequency
Reference 2
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n026 011Ah
Frequency
Reference 3
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n027 011Bh
Frequency
Reference 4
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n028 011Ch
Frequency
Reference 5
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n029 011Dh
Frequency
Reference 6
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n030 011Eh
Frequency
Reference 7
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n031 011Fh
Frequency
Reference 8
0.00 - 9.99hz or 100.0 - 400.0hz 0.00
n032 0120h
Jog Frequency
Reference
0.00 - 9.99hz or 100.0 - 400.0hz 6.00
n033 0121h
Frequency
Reference
Upper Limit
0.0 - 110% 100.0
n034 0122h
Frequency
Reference
Lower Limit
0.0 - 110% 0.0
0 0.01 Hz (< 100Hz); 0.1Hz (100 Hz >=100Hz)
10.1%
2-39 RPM
n035 0123h
Frequency
Reference Unit
Selection
40-
3999
User Setting
0
n036 0124h
Motor Rated
Current
0-150% Of Inverter Rated Output Current
6
0 Standard Motor
1 Standard Motor Short Term
n037 0125h
Electronic
Motor Overload
Protection
2 Disabled
0

Table of Contents