GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
25
Table 5-4 Drive Parameters (continued)
Parameter ADDR Name Set
Description
Default
n038 0126h
Motor Overload
Protection Time
Constant
1 - 60 Minutes 8
0 Operates Only When Drive Is Running
n039 0127h
Cooling Fan
Operation
1 Operates With Power Is ON
0
n040-n049
0128h -
0131h
Reserved
3
1 Run Forward (2 Wire Sequence)
2 Run Reverse (2 Wire Sequence)
3 External Fault (N.O. Contact)
4 External Fault (N.C. Contact)
5 Fault Reset
6 Multi-Speed Reference 1
7 Multi-Speed Reference 2
8 Multi-Speed Reference 3
9 Multi-Speed Reference 4
10 Jog Reference
11 Accel/Decel Time Switch Command
12 External Baseblock (N.O. Contact)
13 External Baseblock (N.C. Contact)
14 Speed Search From Max. Output Frequency
15 Speed Search From Set Frequency
16 Accel/Decel Hold
17 Local/Remote Switch
18 Serial/Terminal Control Switch
19 Emergency Stop Fault (N.O. Contact) (Stop Method n005)
20 Emergency Stop Alarm (N.O. Contact) (Stop Method n005)
21 Emergency Stop Fault (N.C. Contact) (Stop Method n005)
22 Emergency Stop Alarm (N.C. Contact) (Stop Method n005)
23 PID Cancel
24 PID Integral Reset
25 PID Integral Hold
n050 0132h
Multi-Function
Input 1
Terminal S1
26 - 33 Reserved
3
1
n051 0133h
Multi-Function
Input 2
Terminal S2
Same As Parameter n050 2
0 Forward/Reverse
7
n052 0134h
Multi-Function
Input 3
Terminal S3
1 - 25 Others same as parameter n050
3
n053 0135h
Multi-Function
Input 4
Terminal S4
Same As Parameter n050 5
n054 0136h
Multi-Function
Input 5
Terminal S5
Same As Parameter n050 6
n055 0137h
Multi-Function
Input 6
Terminal S6
Same As Parameter n050 7
1 25 Same as parameter n050
34 Up/Down command
8
n056 0138h
Multi-Function
Input 7
Terminal S7
35 Self-Test
10

Table of Contents