GPD315 Modbus RTU Technical Manual TM 4325
Page
5
Chapter 3
GPD315 Communication Parameters
Run/Stop and Frequency Selection
The run/stop and frequency reference commands can originate from serial communication, the
digital operator, or the external terminals. The origin of the run/stop command does not have to
be the same as the origin of the frequency reference command. Parameter n003 (Operation
Method Selection) allows you to set up the origin of the run/stop commands. Parameter n004
(Reference Selection) allows you to set up the origin of the frequency reference command. The
charts below illustrate the possible run/stop and frequency reference selections.
Table 3-1. Run/Stop Selection
Parameter n003 Setting Operation Method Selection
0 Digital Operator
1 External Terminals
2 Serial Communication
The default value of parameter n003 is ‘1’.
Table 3-2. Frequency Reference Selection
Parameter n004 Setting Frequency Reference Selection
0 Digital Operator Pot
1 Digital Operator
2 Voltage Reference (0-10V)
3 Current Reference (4-20mA)
4 Current Reference (0-20mA)
5 Pulse Train Reference
6 Serial Communication
7 Multi-Function Analog Input (0-10V)
8 Multi-Function Analog Input (4-20mA)
9OptionBoard
The default value of parameter n004 is’2’.