GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
21
Monitor Registers (Read Only)
Table 5-3 Monitor Registers
Register Name Bit Description
0 During Run 1: Run 0: Stop
1 Direction 1: Reverse 0: Forward
2 Inverter Ready 1: Ready
3 Fault 1: Fault
4 Data Set Error 1: Error
5 Multi-function output 1 1: Contact ON
6 Multi-function output 2 1: Photo coupler ON
7 Multi-function output 3 1: Photo coupler ON
0020h
Status
Signals
8 - F Not Used
1
0 Overcurrent (OC)
1 Overvoltage (OV)
2 Inverter Overload (OL2)
3 Inverter Overheat (OH)
4 Not Used
1
5 Not Used
1
6 PID Feedback (FbL)
7 External Fault (EF, EF0), Emergency Stop (STP)
8 Hardware Fault (Fxx)
9 Motor Overload (OL1)
A Overtorque Detection (OL2)
B Undertorque Detection (OL3)
C Power Loss (UV1)
D Control Power Supply Fault (UV2)
E MEMOBUS communications Timeout (CE)
0021h
Fault
Content
F Operator Connection Fault (OPR)
0 During Data Writte
1 Not Used
1
2 Not Used
1
3 Limit Fault
4 Matching Fault
5 Not Used
1
6 Not Used
1
7 Not Used
1
0022h
Data Link
Status
8 - F Not Used
1
0023h Frequency Reference
2
0024h Output Frequency
2
0025h – 0026h Reserved
3
0027h Output Current 0.1A
0028h Output Voltage 1V
0029h – 002Ah Reserved
3
0 Terminal S1 1: Contact ON
1 Terminal S2 1: Contact ON
2 Terminal S3 1: Contact ON
3 Terminal S4 1: Contact ON
4 Terminal S5 1: Contact ON
5 Terminal S6 1: Contact ON
6 Terminal S7 1: Contact ON
002Bh
External
Input
Status
7 - F Not Used
1