GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
22
Table 5-3 Monitor Registers (continued)
0 During Run 1: Running
1 During Zero Speed 1: @ Zero Speed
2 Speed Agree 1: @ Speed
3 Minor Fault 1: Minor Fault
4 Frequency Detection 1 1: Output Freq ≤ n095
5 Frequency Detection 2 1: Output Freq ≥ n095
6 Ready 1: Inverter Ready
7 Undervoltage Detection 1: @ Undervoltage
8 Baseblock 1: @ Baseblock
9
Frequency Reference Source 0: Serial
1: Frequency Reference 1 or Analog
A
Run Command Source 0: Serial
1: Operator or External Terminal
B Overtorque Detection 1: Overtorque
C Undertorque Detection 1: Undertorque
D Fault Retry
E Fault 1: Fault
002Ch
Fault
Content
F Serial Communications Timeout 1: Serial Communications Timeout
0 Contact 1: Contact ON
1 Photo Coupler 1 1: Photo Coupler 1 ON
2 Photo Coupler 2 1: Photo Coupler 2 ON
002Dh
External
Terminal
Output
Status
3 - F Not Used
1
002Eh – 0030h Reserved
3
0031h DC Bus Voltage 1vdc
0032h Torque Monitor 100% = Motor Rated Torque
0033h Not Used
1
0034h Not Used
1
0035h Elapsed Time 1hr
0036h Reserved
3
0037h Output Power
4
1W
0038h PID Feedback Capacity ±100%
0039h PID Input Capacity ±100%
003Ah PID Output Capacity ±100%
003Bh – 003Ch Reserved
3
0 CRC Error
1 Data Length Error
2 Not Used
1
3 Parity Error
4 Overrun Error
5 Framing Error
6 Timeout
003Dh
Comm
Error
7 - F Not Used
1
003Eh – 00FFh Reserved
3
0900h Enter