GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
20
Chapter 5
Parameter Tables
Simultaneous Broadcast Registers (Write Only)
Table 5-1 Simultaneous Broadcast Registers
Register Name Bit Description
0 Run Command 1: Run 0: Stop
1 Direction Command 1: Reverse 0: Forward
2 Not Used
1
3 Not Used
1
4 External Fault 1: Fault (EF0)
5 Fault Reset 1: Fault Reset
6 Not Used
1
7 Not Used
1
0001h
Operation
Signals
8 - F Not Used
1
002h Frequency Reference
2
Command Registers (Read/Write)
Table 5-2 Command Registers
Register Name Bit Description
0000h Reserved
0 Run Command 1: Run 0: Stop
1 Direction Command 1: Reverse 0: Forward
2 External Fault 1: Fault (EF0)
3 Fault Reset 1: Fault Reset
4 Multi-function Input Reference 1 (Function selection by n050)
5 Multi-function Input Reference 2 (Function selection by n051)
6 Multi-function Input Reference 3 (Function selection by n052)
7 Multi-function Input Reference 4 (Function selection by n053)
8 Multi-function Input Reference 5 (Function selection by n054)
9 Multi-function Input Reference 6 (Function selection by n055)
A Multi-function Input Reference 7 (Function selection by n056)
0001h
Operation
Signals
B - F Not Used
1
0002h Frequency Reference
2
0003h V/f Gain (1000/100%) 2.0% - 200.0%
0004h – 0008h Reserved
3
0 Multi-function Output 1 (Enabled when n057 = 18) 1: Contact ON
1 Multi-function Output 2 (Enabled when n058 = 18) 1: Photo coupler 1 ON
2 Multi-function Output 3 (Enabled when n059 = 18) 1: Photo coupler 2 ON
0009h
3 - F Not Used
1
000A – 001Fh Reserved
3