GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
35
Chapter 7
Command Priority
Command Priority
The setting of parameter n003 determines the origin of operation commands. This was
discussed in detail in chapter 3, Setting GPD315 Parameters for Communication. Some
commands may be accessed by a source other than the one set up by parameter n003, as
illustrated in the tables 1, 2, and 3 on the following pages.
How to use the Command Priority Tables:
First, determine the source of control you wish to use for your GPD315 drive. Then the n003
parameter should be set up for the desired control you have chosen. (See the table below for
parameter settings.) Select the appropriate Command Priority table on the following pages
based upon what type of operation your drive is set up for.
Table 7-1 n003 Settings
n003 Setting Operation Command Reference Use Table:
0 Digital Operator
7-3
1 External Terminals
7-2
2 Serial Communication
7-1
The left hand column of the Command Priority tables is the source of the operation command
(serial communication, external terminals, and the Digital Operator). The middle column lists the
functions or commands, and the right most column indicates whether the functions are
operational or not available from each source.