GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
26
Table 5-4 Drive Parameters (continued)
Parameter ADDR Name Set
Description
Default
0 @ Fault
1 @ Running
2 @ Speed Agree
3 @ Zero Speed
4 Frequency Detection ≤n095
5 Frequency Detection ≥n095
6 Overtorque Detection (N.O. Contact)
7 Overtorque Detection (N.C. Contact)
8 Reserved
3
9 Reserved
3
10 Minor Fault
11 @ Baseblock
12 @ Run Mode
13 Inverter Ready
14 @ Fault Retry
15 @ Undervoltage
16 @ Reverse
17 @ Speed Search
18 Serial Communications
n057
0132
9h
Multi-Function
Output 1
(MA-MB-MC)
19 @ PID Feedback Loss
1
n058 013Ah
Multi-Function
Output 2
(PHC1-PHCC)
Same As Parameter n057 1
n059 013Bh
Multi-Function
Output 2
(PHC2-PHCC)
Same As Parameter n057 2
n060 013Ch
Analog
Freq. Ref. Gain
0 – 255% 100
n061 013Dh
Analog
Freq. Ref. Bias
±100% 0
n062 013Eh
Analog
Freq. Ref.
Time Constant
0.00 – 2.00 Seconds (0.00 Disables) 0.10
n063 013Fh Reserved
3
n064 0140h Reserved
3
0 Analog Monitor Output
n065 0141h Monitor Output
1 Pulse Monitor Output (±12vdc±10%) (Max. 20mA)
0
0 Output Frequency (10vdc/Max Output Frequency)
1 Output Current (10vdc/Drive Rated Current)
2 DC Bus Voltage (10vdc/400vdc [800vdc])
3 Torque (10vdc/Drive Rated Torque)
n066 0142h Monitor Item
4 Output Power (10vdc/Drive Rated kW)
0
n067 0143h Monitor Gain 0.01 – 2.00 1.00
n068 0144h
Analog
Freq. Ref. Gain
±255% (Operator Voltage Input) 100