3 Utility Function Mode
3.2.27 Advanced Autotuning (Fn201)
3-66
Err4 The torque limit was reached.
When using the torque limit, increase
the torque limit.
Double the set value of the moment of
inertia calculating start level (Pn324).
Err5
While calculating the moment of inertia,
the speed control was set to proportional
control by setting V_PPI in the Option
field to 1.
Operate the SERVOPACK with PI con-
trol while calculating the moment of
inertia.
(cont’d)
Error
Display
Probable Cause Corrective Actions