3.2 Operations
3-47
9
head1
3
Utility Function Mode
(1) Preparation
The following conditions must be met to initialize the vibration detection level.
• The write prohibited setting (Fn010) must not be set to write-protect parameters.
• The test without a motor function must be disabled (Pn00C.0 = 0).
(2) Operating Procedure
Use the following procedure.
• The vibration may not be detected because of improper
servo gains. Also, not all kinds of vibrations can be
detected. Use the detection result as a guideline.
• Set a proper moment of inertia ratio (Pn103). Improper
setting may result in the vibration alarm, warning misde-
tection, or non-detection.
• The references that are used to operate your system must
be input to execute this function.
• Execute this function under the operating condition for
which the vibration detection level should be set.
• Execute this function while the motor speed reaches at
least 10% of its maximum.
Step Display after Operation Keys Operation
1
Press the Key to view the main
menu for the utility function mode.
Use the
or Key to move
through the list and select Fn01B.
2
Press the
Key. The display changes
to the Fn01B execution display.
3
Press the
Key.
“Init” is displayed flashing, and the vibra-
tion level is detected and initialized.
Note: Continues initialization until the
Key is pressed again.
RUN
− FUNCTION−
Fn014:Opt Init
Fn01B:Vibl
−
vl Init
Fn01E:SvMotOp ID
Fn01F:FBOpMot ID
Level Init
RUN
Vibration Detect
Start : [DATA]
Return: [SET]
Level Init
RUN
Vibration Detect
Init