3.2 Operations
3-47
9
head1
3
Utility Function Mode
(1) Preparation
The following conditions must be met to initialize the vibration detection level.
The write prohibited setting (Fn010) must not be set to write-protect parameters.
The test without a motor function must be disabled (Pn00C.0 = 0).
(2) Operating Procedure
Use the following procedure.
The vibration may not be detected because of improper
servo gains. Also, not all kinds of vibrations can be
detected. Use the detection result as a guideline.
Set a proper moment of inertia ratio (Pn103). Improper
setting may result in the vibration alarm, warning misde-
tection, or non-detection.
The references that are used to operate your system must
be input to execute this function.
Execute this function under the operating condition for
which the vibration detection level should be set.
Execute this function while the motor speed reaches at
least 10% of its maximum.
Step Display after Operation Keys Operation
1
Press the Key to view the main
menu for the utility function mode.
Use the
or Key to move
through the list and select Fn01B.
2
Press the
Key. The display changes
to the Fn01B execution display.
3
Press the
Key.
“Init” is displayed flashing, and the vibra-
tion level is detected and initialized.
Note: Continues initialization until the
Key is pressed again.
RUN
FUNCTION
Fn014:Opt Init
Fn01B:Vibl
vl Init
Fn01E:SvMotOp ID
Fn01F:FBOpMot ID
Level Init
RUN
Vibration Detect
Start : [DATA]
Return: [SET]
Level Init
RUN
Vibration Detect
Init