3.2  Operating Procedures for Utility Functions
 3.2.28  Advanced Autotuning without Reference (Fn201)
3-75
7
Press the   Key.
Note: To end the operation by calculat-
ing only the moment of inertia ratio 
without adjusting the gains, press 
the  Key.
The calculated moment of inertia 
will be saved in the SERVOPACK. 
DONE will flash on the display for 
one second, and then the status 
display will return to 1:ADJ.
8
Press the   Key or the   
Key.
Automatic operation will start again 
and the filter and gain will be auto-
matically set. 1:ADJ will flash on the 
display during autotuning.
Note: ERROR will be displayed if there is 
machine resonance or if the 
adjustments cannot be made 
sufficiently for another reason. 
If that occurs, make adjust-
ments using one-parameter 
tuning (Fn203).
If adjustments are completed nor-
mally, the servo will be turned OFF. 
The status display will flash END as 
shown below for approximately two 
seconds and then return to 1:ADJ.
9
Press the   Key.
Note: Press the   Key to cancel 
saving the settings. The display 
will return to the status shown in 
step 1.
The adjusted settings will be saved 
in the SERVOPACK. The status dis-
play will flash DONE as shown 
below for approximately one sec-
ond and then return to 1:A.941.
10
Turn the power supply OFF and ON 
again.
The parameter settings are now 
enabled.
Continued from previous page.
Step Operation Result
1:ADJ               AAT
Pn103 =003 00
Pn100=0100.0 
Pn101=0006.3 6
Pn141=0150.0
END                 AAT
Pn103 =003 00
Pn100=0100.0 
Pn101=0006.3 6
Pn141=0150.0
DONE               AAT
Pn103 =003 00
Pn100=0100.0 
Pn101=0006.3 6
Pn141=0150.0