5 Installation Procedure
YASKAWA ELECTRIC TOBP C730600 95A U1000-Series Option PS-U10 Installation Manual 21
Connection Diagram
Figure 12 illustrates the 24 Vdc Power Supply Option and drive connections.
Figure 12
Figure 12 Connection Diagram for Drive and Option
Wire Gauges and Tightening Torques
Terminal
Number
Screw
Size
Tightening
Torque
Nm
(inlb)
Bare Cable Crimp Terminals
Wire Type
Recomm.
Gauges
mm
2
Applicable
Gauges mm
2
Recomm.
Gauges mm
2
Applicable
Gauges mm
2
24, 0, FE M2
0.22 to 0.25
(1.95 to 2.21)
0.75
(18 AWG)
Standard wire:
0.25 to 1.0
(24 to 17 AWG)
Single line:
0.25 to 1.5
(24 to 16 AWG)
0.5
(20 AWG)
0.25 to 0.5
(24 to 20 AWG)
Shielded
cable, etc.
R/L1
T/L3
S/L2
AC input
Drive
24
0
FE
24 V
0 V
Option
Customer-
Supplied
UL Class 2
24 V Power
Supply Input
CN1
CN19
TB1
TOBP_C730600_95A_2_0_E.fm 21 ページ 2023年2月13日 月曜日 午後1時8分