EasyManuals Logo
Home>YOKOGAWA>Measuring Instruments>AX01C

YOKOGAWA AX01C Installation Manual

YOKOGAWA AX01C
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
(3) Required Lengths of Straight Runs
Based on JIS B 7554 “Electromagnetic Flowmeters” and
our piping condition test data, we recommend the piping
conditions as shown in the following gures. This is not
always enough when the piping line incorporates multiple
conditions at the same time.
F0301.ai
D: Sensor Size
Gate valve
fully open
5D or more
2D
or more
Reducer
pipe
Expander
pipe
0 is allowable. 0 is allowable.
10D or more
2D or more
10D or more
Tee
90-degree bend
Various valves
0 is allowable.5D or more 0 is allowable.5D or more
2D
or more
Figure 3.1.1 Required Lengths of Straight Runs
*1: Do not install anything in the vicinity that may interfere
with the magnetic eld, induced signal voltages, or ow
velocity distributions of the owmeter.
*2: A straight run may not be required on the downstream
side of the owmeter. However, if a downstream valve
or other tting causes irregularity or deviation in ows,
provide a straight run of 2D to 3D on the downstream side.
*3: The valves shall be mounted on the downstream side so
that deviated ows do not occur in the sensor and to avoid
startup from an empty condition.
*4: In case the piping conditions are compounded, install
on the straight pipe section where the upstream part is
sufciently rectied.
(4) Maintaining Stable Fluid Conductivity
IMPORTANT
Do not install the owmeter where uid conductivity
tends to become uneven. If chemicals are fed near
the upstream side of a magnetic owmeter, they may
affect the ow rate’s indications. To avoid this situation,
it is recommended that the chemical feed ports be
located on the downstream side of the owmeter. If
it is unavoidable that chemicals must be fed on the
upstream side, provide a sufcient length of straight
run (approximately 50D or more) to ensure the proper
mixture of uids.
F0302.ai
(Incorrect)
Upstream side
(Correct)
Downstream side
Figure 3.1.2 Chemical Injection
(5) Precautions for Use of Liquid Sealing
Compounds
IMPORTANT
Care must be taken in using liquid sealing compounds
on the piping, as it may have a negative inuence on
the ow indications by owing out and covering the
surfaces of an electrode or grounding ring. In particular,
care must be taken if a liquid sealing compound is used
in the case of vertical piping.
(6) Service Area
Select locations where there is adequate space to service
installing, wiring, overhauling, etc.
(7) Bypass Line
It is recommended to install a bypass line to facilitate
maintenance and zero adjustment.
F0303.ai
Bypass valve
Block valve
Block
valve
Figure 3.1.3 Bypass Line
(8) Supporting the Flowmeter
CAUTION
Do not secure the owmeter separately to prevent the
vibrations, shocks, and expansion and contraction forces
of the piping from affecting it. Fix the pipes rst, then
support the owmeter with the pipes.
<3. Installation>
10
IM 01E24A01-01EN

Other manuals for YOKOGAWA AX01C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA AX01C and is the answer not in the manual?

YOKOGAWA AX01C Specifications

General IconGeneral
BrandYOKOGAWA
ModelAX01C
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals