<7. Operation>
7-10
IM 01C25B01-01E
7.6.7 Pressure LRV/URV Conguration
Pressure LRV and URV can be set. The number for each digit is changed by turning the zero-adjustment
screwandsetbypressingthepushbutton.Pleasereferto7.6.8DampingTimeConstantCongurationfor
how to change the numerical value.
When the setting is out of the limit, an alarm will be generated.
7.6.8 Damping Time Constant Conguration
Thedampingtimeconstantfortheamplierassemblycanbeset.QuickResponseParameterisautomatically
set to ON when the damping time constant is set to less than 0.5 seconds. Damping time constant is rounded
o󰀨totwodecimalplaces.
F0714.ai
screw
Change the first digit
Set all other
characters in the
same way
Setting range: 0.00 to 100.00 (seconds)
Blinking Blinking Blinking
Save ?/
Cancel ?
push
Go to the next
Character
7.6.9 Output Mode Conguration
Pressure Output Mode (Linear or Sq root) can be selected by turning the zero-adjustment screw. Please refer
to7.6.6PressureUnitCongurationforhowtoselectandsettheenumeratedvalue.
7.6.10 Display Out 1 Conguration
Display Out1 can be selected by turning the zero-adjustment screw. Please refer to 7.6.6 Pressure Unit
Congurationforhowtoselectandsettheenumeratedvalue.