MODBUS Communication
32
TI 12A01F01-62EN
3.1 Alarm list (Converter)
Alarm bit Alarm name
Alarm
Number
default*1 Note
Measurement alarm
31 Hardware failure 0001 (F)
30 Internal com. erro 0002 (F)
29 IO mod. param. read error 0003 (F)
28 Com. mod. param. read err 0004 (F)
27 CPU param. read error 0005 (F)
14 VGB calc. error 0010 F *2
13 Ratio calc. error 0011 F *2
12 Passage calc. error 0012 F *2
11 Rejection calc. error 0013 F *2
10 Deviation calc. error 0014 F *2
3 Script Error 1 0015 N *2
2 Script Error 2 0016 N *2
1 Script Error 3 0017 N *2
0 Script Error 4 0018 N *2
I/O alarm
31 mA output burn low 1 0030 (N) *3
30 mA output burn low 2 0031 (N) *3
29 mA output burn low 3 0032 (N) *3
28 mA output burn low 4 0033 (N) *3
27 mA output burn high 1 0034 (N) *3
26 mA output burn high 2 0035 (N) *3
25 mA output burn high 3 0036 (N) *3
24 mA output burn high 4 0037 (N) *3
23 mA1 output saturation 1 0038 (S)
22 mA1 output saturation 2 0039 (S)
21 mA1 output saturation 3 003A (S)
20 mA1 output saturation 4 003B (S)
15 AI exceed upper limit 0040 (S)
14 AI exceed lower limit 0041 (S)
13 AI out of range 0042 (F)
11 Expiry time exceeded 1 0043 (M)
10 Expiry time exceeded 2 0044 (M)
9 Expiry time exceeded 3 0045 (M)
8 Expiry time exceeded 4 0046 (M)
7 Fail safe occur 0047 F
Mantenance Status
20 Simulated mA value 1 0070 (C)
19 Simulated mA value 2 0071 (C)
18 Simulated mA value 3 0072 (C)
17 Simulated mA value 4 0073 (C)
16 Outputs in HOLD 1 0074 N
15 Outputs in HOLD 2 0075 N
14 Outputs in HOLD 3 0076 N
13 Outputs in HOLD 4 0077 N
10 Wash response failure 1 0078 M
9 Wash response failure 2 0079 M
8 Wash response failure 3 007A M
7 Wash response failure 4 007B M
6 Simulated contact value 1 007C (C)
5 Simulated contact value 2 007D (C)
4 Simulated contact value 3 007E (C)
3 Simulated contact value 3 007F (C)
Apr. 19, 2019-00