Setting a Voltage Input Type and Display Scale (for UT150/UT152/UT155
only)
The following operating procedure describes an example of setting “1 to 5V DC voltage
input signals” for the measured input type, and “0.0 to 500.0” for the display scale.
Step 1:
The parameter "IN" (measured input type)
appears at power on.
UT150/UT152/UT155
Display example
Flashes during change.
Step 2:
Press the or key to set the required
setpoint for the measured input type. The
measured input type is set using a range code.
(See Page 4-1)
The period flashes while the value is being
changed. In this example, "1 to 5V DC" (setpoint:
22) is set for the measured input type.
To the next page
Step 4:
Press the key for 3 seconds or more to display
the parameter "A1".
The parameter "A1" appears only for the controller
with the "/AL" or" /HBA" option.
The parameter "CTL" appears for the controller
without the "/AL" or" /HBA" option.
Step 3:
Press the key once to register the setpoint. The
operating display appears automatically.
The Step 4 onwards describes the procedure to set a
display scale. The display scale is changed from "0.0
to 100.0 "(factory-set default) to "0.0 to 500.0".
Step 5:
Press the key several times to display the
parameter "LOC."
Set "-1" to enter the setup parameter
setting display. But if "LOC" = 1 or 2 is
already set, the parameter value can not
be changed by setting "LOC" = -1 only. To
change the parameter value, set "LOC" = 0
at first (for disabling key lock), then set
"LOC" = -1 once again
NOTE
Step 6:
Press the or key to display "-1."
Flashes during change.
<Operating Procedure>

Table of Contents

Other manuals for YOKOGAWA UT130

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UT130 and is the answer not in the manual?

YOKOGAWA UT130 Specifications

General IconGeneral
BrandYOKOGAWA
ModelUT130
CategoryTemperature Controller
LanguageEnglish

Related product manuals