036-21548-001-D-0405
Unitary Products Group 11
TABLE 6: DNZ042 COOLING CAPACITIES - 3-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,150 CFM 1,400 CFM
WB °F WB °F
72 67 62 57 72 67 62 57
85 °F
NET CAP. MBH 45.4 42.9 39.9 39.7 45.6 43.2 40.1 39.9
TOTAL POWER kW 3.26 3.23 3.22 3.17 3.47 3.45 3.43 3.38
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 27.2 35.3 39.9 39.7 30.9 39.8 40.1 39.9
83 24.0 32.1 39.3
39.7 26.8 35.7 40.1 39.9
80 20.7 28.8 36.1 36.9 22.7 31.6 39.6 40.6
77 17.4 25.5 32.8 33.7 18.6 27.5 35.5 36.5
74 14.1 22.2 29.5 30.4 14.5 23.5 31.4 32.4
71 -- 19.0 26.2 27.1 -- 19.4 27.4 28.3
68 -- 15.7 23.0 23.8 -- 15.3 23.3 24.2
95 °F
NET CAP. MBH 43.1 40.2 37.2 37.5 43.6 40.7 37.7 38.0
TOTAL POWER kW 3.59 3.55 3.51 3.49 3.80 3.76 3.72 3.70
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 26.3 34.3 37.2 37.5 30.3 39.2 37.7 38.0
83 23.1 31.1 37.2 37.5 26.2 35.1 37.7 38.0
80 19.8 27.8 34.3 34.5 22.1 31.0 38.3 38.6
77 16.5 24.5 31.0 31.3 18.0 27.0 34.3 34.5
74 13.2 21.2 27.8 28.0 13.9 22.9 30.2 30.4
71 -- 17.9 24.5 24.7 -- 18.8 26.1 26.3
68 -- 14.7 21.2 21.4 -- 14.7 22.0 22.3
105 °F
NET CAP. MBH 39.9 36.7 34.5 34.7 40.6 37.3 35.1 35.3
TOTAL POWER kW 3.99 3.95 3.84 3.88 4.20 4.16 4.05 4.09
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 25.5 33.0 34.5 34.7 29.4 36.5 35.1 35.3
83 22.2 29.7
34.5 34.7 25.3 33.7 35.1 35.3
80 19.0 26.5 32.0 32.1 21.3 29.7 35.9 35.9
77 15.7 23.2 28.8 28.8 17.2 25.6 31.8 31.8
74 12.4 19.9 25.5 25.5 13.1 21.5 27.7 27.8
71 -- 16.6 22.2 22.2 -- 17.4 23.7 23.7
68 -- 13.3 18.9 18.9 -- 13.3 19.6 19.6
115 °F
NET CAP. MBH 36.7 33.1 31.7 32.0 37.6 33.9 32.5 32.7
TOTAL POWER kW 4.39 4.34 4.18 4.28 4.60 4.55 4.38 4.48
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 24.7 31.7 31.7 32.0 28.6 33.9 32.5 32.7
83 21.4 28.4
31.7 32.0 24.5 32.4 32.5 32.7
80 18.1 25.1 29.7 29.6 20.4 28.3 33.5 33.3
77 14.9 21.9 26.5 26.3 16.3 24.2 29.4 29.2
74 11.6 18.6 23.2 23.0 12.2 20.1 25.3 25.1
71 -- 15.3 19.9 19.7 -- 16.0 21.2 21.0
68 -- 12.0 16.6 16.4 -- 12.0 17.1 16.9
125 °F
NET CAP. MBH 33.5 29.6 29.0 29.3 34.5 30.5 29.8 30.1
TOTAL POWER kW 4.79 4.74 4.51 4.67 5.00 4.95 4.71 4.88
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 23.9 30.4 29.0 29.3 27.7 31.2 29.8 30.1
83 20.6 27.1
29.0 29.3 23.6 31.0 29.8 30.1
80 17.3 23.8 27.5 27.1 19.6 26.9 31.0 30.6
77 14.0 20.5 24.2 23.8 15.5 22.8 26.9 26.5
74 10.8 17.3 20.9 20.5 11.4 18.8 22.9 22.4
71 -- 14.0 17.6 17.2 -- 14.7 18.8 18.3
68 -- 10.7 14.3 14.0 -- 10.6 14.7 14.3
1.
These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity.