036-21548-001-D-0405
Unitary Products Group 9
TABLE 4: DNZ030 COOLING CAPACITIES - 2-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,000 CFM 1,250 CFM
WB °F WB °F
72 67 62 57 72 67 62 57
85 °F
NET CAP. MBH 32.7 31.0 28.7 28.7 33.3 31.6 29.2 29.2
TOTAL POWER kW 2.10 2.10 2.10 2.09 2.28 2.29 2.29 2.27
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 22.2 27.8 28.7 28.7 25.7 31.6 29.2 29.2
83 19.3 24.9
28.7 28.7 21.9 28.2 29.2 29.2
80 16.4 22.0 27.2
28.7 18.2 24.4 29.2 29.2
77 13.5 19.0 24.3 25.8 14.5 20.7 25.4 25.5
74 10.5 16.1 21.4 22.9 10.8 17.0 21.7 21.8
71 -- 13.2 18.5 20.0 -- 13.2 18.0 18.0
68 -- 10.3 15.6 17.1 -- 9.5 14.2 14.3
95 °F
NET CAP. MBH 31.2 29.2 26.6 26.8 31.8 29.7 27.2 27.4
TOTAL POWER kW 2.36 2.36 2.35 2.33 2.55 2.54 2.53 2.51
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 21.8 27.3 26.6 26.8 25.2 29.7 27.2 27.4
83 18.9 24.4
26.6 26.8 21.5 27.7 27.2 27.4
80 15.9 21.5 26.3
26.8 17.8 24.0 27.2 27.4
77 13.0 18.6 23.4 23.9 14.1 20.3 23.4 23.7
74 10.1 15.7 20.5 21.0 10.3 16.5 19.7 19.9
71 -- 12.8 17.5 18.1 -- 12.8 16.0 16.2
68 -- 9.9 14.6 15.2 -- 9.1 12.3 12.5
105 °F
NET CAP. MBH 28.9 26.6 24.7 24.9 29.5 27.2 25.1 25.4
TOTAL POWER kW 2.67 2.66 2.65 2.64 2.85 2.85 2.83 2.82
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 21.0 25.7 24.7 24.9 24.6 27.2 25.1 25.4
83 18.1 23.4
24.7 24.9 20.9 26.1 25.1 25.4
80 15.2 20.5 24.5
24.9 17.2 23.2 25.1 25.4
77 12.3 17.6 21.6 22.0 13.4 19.5 21.4 21.7
74 9.3 14.7 18.7 19.1 9.7 15.8 17.7 18.0
71 -- 11.8 15.8 16.2 -- 12.1 14.0 14.2
68 -- 8.9 12.8 13.3 -- 8.3 10.2 10.5
115 °F
NET CAP. MBH 26.7 24.1 22.7 23.0 27.2 24.6 23.1 23.4
TOTAL POWER kW 2.97 2.97 2.94 2.94 3.16 3.16 3.13 3.13
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 20.2 24.1 22.7 23.0 24.0 24.6 23.1 23.4
83 17.3 22.5
22.7 23.0 20.3 24.6 23.1 23.4
80 14.4 19.5
22.7 23.0 16.6 22.5 23.1 23.4
77 11.5 16.6 19.8 20.1 12.8 18.7 19.4 19.7
74 8.6 13.7 16.9 17.2 9.1 15.0 15.6 16.0
71 -- 10.8 14.0 14.3 -- 11.3 11.9 12.3
68 -- 7.9 11.0 11.4 -- 7.6 8.2 8.5
125 °F
NET CAP. MBH 24.5 21.6 20.8 21.2 24.9 22.0 21.1 21.5
TOTAL POWER kW 3.28 3.28 3.24 3.25 3.47 3.47 3.43 3.44
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 19.5 22.5 20.8 21.2 23.4 22.0 21.1 21.5
83 16.5 21.5
20.8 21.2 19.7 23.0 21.1 21.5
80 13.6 18.6 20.9
21.2 15.9 21.7 21.1 21.5
77 10.7 15.6 18.0 18.2 12.2 18.0 17.3 17.8
74 7.8 12.7 15.1 15.3 8.5 14.3 13.6 14.0
71 -- 9.8 12.2 12.4 -- 10.5 9.9 10.3
68 -- 6.9 9.3 9.5 -- 6.8 6.2 6.6
1.
These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity.
ALL SENSIBLE CAPACITY