036-21548-001-D-0405
8 Unitary Products Group
TABLE 3: DNZ024 COOLING CAPACITIES - 2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
800 CFM 1,000 CFM
WB °F WB °F
72 67 62 57 72 67 62 57
85 °F
NET CAP. MBH 28.7 26.7 24.6 24.2 29.7 27.7 25.5 25.1
TOTAL POWER kW 1.99 1.98 1.98 1.96 2.15 2.13 2.14 2.11
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 18.8 22.7 24.6 24.2 22.3 26.8 25.5 25.1
83 16.4 20.4
24.6 24.2 19.3 23.8 25.5 25.1
80 14.1 18.0 22.3
24.2 16.3 20.8 25.5 25.1
77 11.8 15.7 20.0 21.9 13.3 17.8 22.5 22.1
74 9.4 13.4 17.7 19.6 10.3 14.9 19.5 19.2
71 -- 11.0 15.3 17.2 -- 11.9 16.5 16.2
68 -- 8.7 13.0 14.9 -- 8.9 13.5 13.2
95 °F
NET CAP. MBH 27.4 25.5 23.2 22.7 28.1 26.2 23.8 23.3
TOTAL POWER kW 2.23 2.23 2.21 2.16 2.31 2.31 2.29 2.24
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 18.7 22.9 23.2 22.7 21.5 26.2 23.8 23.3
83 16.3 20.6
23.2 22.7 18.5 23.2 23.8 23.3
80 14.0 18.2 22.2
22.7 15.5 20.2 23.8 23.3
77 11.7 15.9 19.9 20.4 12.6 17.3 20.8 20.4
74 9.3 13.6 17.6 18.1 9.6 14.3 17.8 17.4
71 -- 11.2 15.2 15.7 -- 11.3 14.9 14.4
68 -- 8.9 12.9 13.4 -- 8.3 11.9 11.4
105 °F
NET CAP. MBH 25.5 23.1 20.9 21.1 26.3 23.9 21.6 21.8
TOTAL POWER kW 2.51 2.50 2.47 2.44 2.61 2.61 2.58 2.54
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 17.8 21.8 20.9 21.1 20.9 23.9 21.6 21.8
83 15.5 19.5
20.9 21.1 18.0 22.4 21.6 21.8
80 13.1 17.1 20.4
21.1 15.0 19.6 21.6 21.8
77 10.8 14.8 18.1 18.8 12.0 16.6 18.6 18.8
74 8.5 12.5 15.8 16.5 9.0 13.6 15.6 15.9
71 -- 10.1 13.4 14.1 -- 10.6 12.6 12.9
68 -- 7.8 11.1 11.8 -- 7.6 9.7 9.9
115 °F
NET CAP. MBH 23.5 20.7 18.6 19.5 24.5 21.6 19.4 20.3
TOTAL POWER kW 2.79 2.78 2.74 2.72 2.91 2.90 2.86 2.85
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 16.9 20.7 18.6 19.5 20.4 21.6 19.4 20.3
83 14.6 18.4
18.6 19.5 17.4 21.6 19.4 20.3
80 12.3 16.1
18.6 19.5 14.4 18.9 19.4 20.3
77 9.9 13.7 16.3 17.2 11.4 15.9 16.4 17.3
74 7.6 11.4 13.9 14.8 8.4 12.9 13.4 14.3
71 -- 9.1 11.6 12.5 -- 9.9 10.4 11.4
68 -- 6.7 9.3 10.2 -- 6.9 7.4 8.4
125 °F
NET CAP. MBH 21.6 18.3 16.3 17.9 22.7 19.2 17.2 18.8
TOTAL POWER kW 3.06 3.05 3.00 3.00 3.21 3.20 3.14 3.15
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 16.0 19.6 16.3 17.9 19.8 19.2 17.2 18.8
83 13.7 17.3
16.3 17.9 16.8 20.7 17.2 18.8
80 11.4 15.0 16.8
17.9 13.8 18.2 17.2 18.8
77 9.1 12.6 14.5 15.5 10.9 15.2 14.2 15.8
74 6.7 10.3 12.1 13.2 7.9 12.2 11.2 12.8
71 -- 8.0 9.8 10.9 -- 9.2 8.2 9.8
68 -- 5.6 7.5 8.5 -- 6.3 5.2 6.8
1.
These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity.
ALL SENSIBLE CAPACITY