FORM 100.10-NOM2
29
YORK INTERNATIONAL
WIRING DIAGRAM
STARTER PANEL
NOTES: 1. Connect remote control signal for starter fan at Terminals 1 & 2. Dry control contact rated at min. 2A / 115V.
2. Connect remote control signal for (optional) return fan at Terminals 3 & 4. Dry control contact rated at min.
2A / 115V.
3. Remove Jumper J1 for independent control of motors.
4. Install safeties between Terminals 5 & 6 or 7 & 8. Remove Jumpers J2 and J3, accordingly.
5. TB not installed if internal rotary (thru-the-door) disconnect is present.
6. TB1 to be used on units when the disconnect is 100 amp, or less. Above 100 amp, L4 & L5 the disconnect
lugs are to be tapped.
460V
3T
120V
115V
(OPTIONAL SINGLE-POINT
LIGHT CIRCUIT)
LD06281
(NOTE 6)
MAXIMUM FUSE SIZES
120 VOLT
OPTION
3T
FU4
FU41
CURRENT
AVAILABLE
CODE
2KVA 20 AMP NONE 16 AMP H7
FIG. 33 – WIRING DIAGRAM STARTER PANEL