Loading...
BLOWER
SPEED,
(RPM)
MOTOR
PULL
EY
(TURNS
OPEN)*
AIRFLOW
2.80 m
3
/s 3.30 m
3
/s 3.80 m
3
/s 4.10 m
3
/s 4.40 m
3
/s
ESP
(P
a)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
HIGH STATIC DRIVE (m
3
/s)
895 6.0 312 3.5 4.0 268 3.7 4.3 198 4.2 4.8 143 4.6 5.2 79 5.1 5.8
930 5.0 362 3.7 4.3 318 4.0 4.5 248 4.5 5.1 193 4.9 5.6 129 5.4 6.2
970 4.0 421 4.0 4.5 377 4.2 4.9 306 4.8 5.5 252 5.2 6.0 187 5.8 6.6
1005 3.0 473 4.2 4.8 429 4.5 5.1 359 5.1 5.8 304 5.6 6.4 240 6.1 7.0
1045 2.0 535 4.4 5.0 491 4.8 5.5 420 5.4 6.2 365 5.9 6.8 - - -
1080 1.0 590 4.6 5.3 546 5.0 5.8 475 5.7 6.5 420 6.2
7.1 - - -
BLOWER
S
PEED,
(RPM)
MOTOR
PULL
EY
(TURNS
OPEN)*
AIRFLOW
5930 CFM 6990 CFM 8050 CFM 8685 CFM 9320 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg
)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
HIGH STATIC DRIVE (CFM)
895 6.0 1.3 4.7 4.0 1.1 5.0 4.3 0.8 5.6 4.8 0.6 6.1 5.2 0.3 6.8 5.8
930 5.0 1.5 5.0 4.3 1.3 5.3 4.5 1.0 6.0 5.1 0.8 6.6 5.6 0.5 7.2 6.2
970 4.0 1.7 5.3 4.5 1.5 5.7 4.9 1.2 6.4 5.5 1.0 7.0 6.0 0.8 7.8 6.6
1005 3.0 1.9 5.6 4.8 1.7 6.0 5.1 1.4 6.8 5.8 1.2 7.4 6.4 1.0 8.2 7.0
1045 2.0 2.1 5.9 5.0 2.0 6.4 5.5 1.7 7.3 6.2 1.5 7.9 6.8 - - -
1080 1.0 2.4 6.2 5.3 2.2 6.8 5.8 1.9 7.7 6.5 1.7 8.4 7.1 - - -
5120416-XIM-C-0216
32 Johnson Controls Unitary Products
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 16 for additional static resistances.
ESP = External Static Pressure available fo
r the supply and return air duct system. All internal unit resistances have been deducted from the total static
pressure of the blower.
* Do
NOT close the pulley below 1 turn open.
** Factory setting.