BLOWER
SPEED,
(RPM)
MOTOR
PULL
EY
(TURNS
OPEN)*
AIRFLOW
2.10 m
3
/s 2.45 m
3
/s 2.80 m
3
/s 3.10 m
3
/s 3.40 m
3
/s
ESP
(P
a)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
HIGH STATIC DRIVE (m
3
/s)
1030 6.0 378 2.3 2.7 321 2.7 3.2 258 3.2 3.8 199 3.6 4.4 134 4.2 5.0
1070 5.0 417 2.4 2.9 361 2.9 3.4 299 3.4 4.1 240 3.9 4.7 - - -
1115 4.0 461 2.6 3.1 407 3.1 3.7 345 3.7 4.4 286 4.2 5.0 - - -
1155 3.0 502 2.8 3.3 448 3.3 4.0 387 3.9 4.7 - - - - - -
1200 2.0 548 3.0 3.6 495 3.6 4.3 435 4.2 5.0 - - - - - -
1240 1.0 590 3.2 3.8 538 3.8 4.6 - - - - -
- - - -
BLOWER
S
PEED,
(RPM)
MOTOR
PULL
EY
(TURNS
OPEN)*
AIRFLOW
4450 CFM 5190 CFM 5930 CFM 6565 CFM 7200 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg
)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
HIGH STATIC DRIVE (CFM)
1030 6.0 1.5 3.1 2.7 1.3 3.6 3.2 1.0 4.3 3.8 0.8 4.9 4.4 0.5 5.6 5.0
1070 5.0 1.7 3.3 2.9 1.4 3.8 3.4 1.2 4.5 4.1 1.0 5.2 4.7 - - -
1115 4.0 1.9 3.5 3.1 1.6 4.1 3.7 1.4 4.9 4.4 1.2 5.6 5.0 - - -
1155 3.0 2.0 3.7 3.3 1.8 4.4 4.0 1.6 5.2 4.7 - - - - - -
1200 2.0 2.2 4.0 3.6 2.0 4.8 4.3 1.7 5.6 5.0 - - - - - -
1240 1.0 2.4 4.3 3.8 2.2 5.1 4.6 - - - - - - - - -
5120416-XIM-C-0216
Johnson Controls Unitary Products 33
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available fo
r the supply and return air duct system. All internal unit resistances have been deducted from the total static
pressure of the blower.
* Do
NOT close the pulley below 1 turn open.
** Factory setting.
Supply Air Blower Performance (15 Ton) - Gas Heat 180 Mbh - Bottom Duct Connections