SM-18001-rev.1
5-7
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(2) RemoteON/OFF2(PulseSignalInput)[InputSetting:Code(04)]
ThisisanON/OFFfunctionfromaremoteplacebyusingpulsesignals.Anexampleofabasicwiring
andtimechartisshownbelow.
ON
X1
OFF
X2
Power
Supply
Control Circuit
Indoor Unit PCB
CN3
X1
X2
3P Connector
3
2
1
3
2
1
NOTES:
The pulse range is 200ms or more.
Wiring Diagram Example of Remote ON/OFF 2
Example: Operation Input is set to terminals 2 and 3 of CN3.
Stoppage Input is set to terminals 1 and 2 of CN3.
( )
Signal to terminals 2 & 3 of CN3 (Operation)
Signal to terminals 1 & 2 of CN3 (Stop)
NOTE:
Operation priority is given to the remote
ON/OFF signal or wired controller
signal which is given last.
Control by Wired Controller
Unit Operation
Time Chart
Ti
me
Example: Operation Input is set to terminals 2 and 3 of CN3.
Stoppage Input is set to terminals 1 and 2 of CN3.
( )
NOTES:
1.Pickingupsignalwithin10secondsafterpowersupplyisturnedONisnotpossibleduetoinitialization
ofthecomponents.
Donotchangethesignal(ON/OFF)inthisperiod.
2.WiredControllerisrequiredforthisfunction.
3.Ifmultipleindoorunitsareconnectedtothesamecommunicationcableforwiredcontroller,inputthe
signaltoanyoftheseindoorunits.
4.Whenthecommunicationcableisnotusedinthetwin,tripleandquadcombinationsforsimultaneous
operation,inputthesignaltothemainindoorunit.