EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(1) QuickFunction
Thisfunctionisusedwhendecreasing/increasingtheindoortemperaturequickly.
Thisfunctionoperatesasfollowsfor30minutesfromtheoperationstart-up.
ThisfunctionisonlyavailablewhentheoperationmodeisCOOLorHEAT.
Theunitstartseachtimeinquickmodeuntilthesettingiscanceled.
(2) PowerUpSetting
Ifthecooling/heatingcapacityseemsinsufcientduringthenormaloperation,setthisfunction.
Bysettingthisfunction,thetargetfrequencyandupperlimitofthecompressoraresethigheras
follows.
SettingCondition
CompressorFrequency
Indoor Fan
UpperLimit TargetFrequency VariationWidth
DefaultSetting - - - -
COOL DefaultSetting+20% DefaultSetting+20% DefaultSetting+200% Automatically
HEAT DefaultSetting+20% DefaultSetting+20% DefaultSetting+50% -
SettingCondition
PowerUpMode
CompressorFrequencyforCoolingOperation CompressorFrequencyforHeatingOperation
UpperLimit TargetFrequency UpperLimit TargetFrequency
0(DefaultSetting) - - - -
1 DefaultSetting+20% DefaultSetting+20% - -
2 - - DefaultSetting+20% DefaultSetting+20%
3 DefaultSetting+20% DefaultSetting+20% DefaultSetting+20% DefaultSetting+20%
NOTES:
1. Ifthisfunctionisset,indoorfanspeedisautomaticallycontrolledregardlessfanspeedsettingfrom
wiredcontroller.(Ifthereisanupper/lowerlimitofairow,donotusethisfunction.)
IncaseofDucted(EconoFresh),donotusethisfunction.IfitisusedforDucted(EconoFresh),the
thermalloadoftheroommaysignicantlyincreasedependingontheoutdoortemperatureconditions.
2. TheupperlimitandtargetfrequencyofthecompressoraresameasFunctionSetting“Hc”or“Hh”.
3. Thisfunctionmayincreasepowerconsumption.
NOTE:
TheupperlimitandtargetfrequencyofthecompressoraresameasFunctionSetting“Hc”or“Hh”.
5.5.4 ComfortFunction
Followingfunctionsarenotavailabledependingonconnectedoutdoorunit.