SM-18001-rev.1
3-7
TROUBLESHOOTING
DIP Switch Settings
(1) Turn OFF the power supply of the indoor unit and the outdoor unit before DIP switch setting. Not doing
so makes the setting invalid.
(2) Factory settings for DSW6 and RSW1 are set to “0”. If connecting the indoor unit to H-LINK II
supporting the outdoor unit without setting any DIP switches, auto-address setting is performed by the
wired controller.
(3) Auto-Address Setting by Wired Controller
The address numbering is started from “0” by the auto-address function when the wired controller is
connected to H-LINK II.
● Ducted High Static
● Ducted Medium Static and Slim
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
ON
123456
ON
1234
ON
12
ON
123456
ON
123456
ON
12
ON
123
DSW7
DSW3
DSW9
DSW8
DSW4
DSW5
RSW2
RSW1
DSW6
RSW1
(Indoor Unit No. Setting)
RSW2
(Refrigerant Cycle No.Setting)
DSW7 (Fuse Recover)
DSW4 (Unit Model Code Setting)
DSW8 (Optional Function Setting)
DSW9 (Optional Function Setting)
DSW3 (Capacity Code Setting)
DSW5 (Refrigerant Cycle No. Setting)
DSW6
PCB1
(Indoor Unit No. Setting)
DSW3
ON
1 234
DSW4
ON
1234
RSW2
0
9
8
7
6
5
4
3
2
1
RSW1
0
9
8
7
6
5
4
3
2
1
DSW6
ON
123456
DSW5
ON
1 23456
DSW7
ON
12
RSW1
(Indoor Unit No. Setting)
RSW2
(Refrigerant Cycle No. Setting)
DSW4 (Unit Model Code Setting)
DSW3 (Capacity Code Setting)
DSW5
(Refrigerant Cycle No. Setting)
DSW6 (Indoor Unit No. Setting)
DSW7
(Fuse Recover)
ON
123
DSW8
DSW8
(Unit Model Code Setting)
3.1.3 Checking Rotary Switch and DIP Switch Settings
The following diagram indicates the factory settings of DSWs on PCBs in the indoor and outdoor units.
When simultaneous operation control of multiple units or room thermostat control is operated, the DSW
setting will be different as shown below.
(1) Outdoor Unit (Factory Setting)
Refer to the Service Manual for Outdoor Unit.
(2) Indoor Unit (Factory Setting)
The positions of the DIP switches on the PCB are shown in the gure below. Turn OFF all power
supplies before setting.
Without turning OFF all power supplies, the switches do not work and the settings are invalid.
The “
n
” mark indicates the position of DIP switches.