SM-18001-rev.1
5-17
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.2.1 FunctionSelectionItem
5.4.2 FunctionSetting
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents
1 b1
CancellationofHeating
TemperatureCompensation
duetoUnevenHeatLoad
00
01
02
03
04
Standard(SetTemp.+7
o
F(+4
o
C))
Removal(SetTemp.)
SetTemp.+3
o
F(+2
o
C)(*1)
SetTemp.+5
o
F(+3
o
C)
SetTemp.+2
o
F(+1
o
C)
2 b2
CirculatorFunctionduring
HeatingThermo-OFF
00
01
NotAvailable
Available
3 b3 Not Prepared - - NotUsed(Useas00conditions)
4 b4 ChangeofFilterCleaningTime -
00
01
02
03
04
Standard1,200hrs(Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5 b5 FixingofOperationMode
×
00
01
Standard
Fixed
6 b6 FixingofSettingTemperature
×
00
01
Standard
Fixed
7 b7
FixingofOperationas
ExclusiveCoolingUnit
×
00
01
Standard
Fixed
8 b8 AutomaticCOOL/HEATOperation
×
00
01
NotAvailable
Available
9 b9 FixingofFanSpeed
×
00
01
Standard
Fixed
10 bA Not Prepared - - Not Used
11 bb
CoolingTemperatureCompensation
duetoUnevenHeatLoad
×
00
01
02
Standard(NoCompensation)
SetTemp.–2
o
F(–1
o
C)
SetTemp.–3
o
F(–2
o
C)
12 bC Not Prepared - - NotUsed(Useas00conditions)
13 bd Not Prepared - - NotUsed(Useas00conditions)
14 bE Not Prepared - - NotUsed(Useas00conditions)
15 C1 Not Prepared - - NotUsed(Useas00conditions)
16 C2 Not Prepared - - Not Used
17 C3 Not Prepared - - Not Used
18 C4 Not Prepared - - Not Used
19 C5
Hi Speed
(ExceptforHiSpeedduringHeating
Thermo-OFF)
00
01
02
NotAvailable
Hi Speed 1
Hi Speed 2
20 C6
HiSpeedduringHeating
Thermo-OFF
00
01
NotAvailable
Available
21 C7
CancelingofEnforced3Minutes
MinimumOperationTimeof
Compressor
00
01
Standard
Cancelation
22 C8 ThermistorofWiredController(*6)
00
01
02
00
01
02
<IfWiredControllerThermistorisSelected˃
NotAvailable
ControlbyThermistorofWiredController
ControlbyAverageValueofIndoorSuction
ThermistorandThermistorofWiredController
<IfRemoteSensorisSelected˃
ControlbyAverageValueofIndoorSuction
ThermistorandRemoteSensor
ControlbyRemoteSensor
Sameas"00"
23 C9 Not Prepared - - Not Used
24 CA Not Prepared - - Not Used
25 Cb SelectionofForcedStoppageLogic
×
00
01
ForcedStoppageInput:AContact
ForcedStoppageInput:BContact