5-38
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.5 Functions from Wired Controller
ThefunctionsareavailablefromthewiredcontrollerCIW01asfollows.
Regardingsettingprocedure,refertothe“OperationManual”fortheWiredController.
5.5.1 PowerSavingFunction
NOTE:
Thefollowingfunctions(1)~(3)cannotbeoperatedatthesametime.
(1) OutdoorUnitCapacityControl
Thedemandfunctionsettingcanbecontrolledfromwiredcontroller.Selectfrom“PeakCutControl”
and“ModerateControl”accordingtothesituation.
NOTES:
1. Thepowersetvalue(%)isjustacriterion.Thepowersetvalueforthisfunctionisdifferentfromthe
actualpowervalueinprecision.Usethedemandcontroller(option)whenitisnecessarytomanage
themaximumpowercorrectly.
2. Thecoolingcapacityisdecreasedaccordingtothepowersavingsettingvalueforthereducingof
compressormotorrevolution.
3. Theactualelectricalpowerconsumptionmaybehigherthanthevaluedisplayedonthescreenunder
certainoperatingconditionsuchasprotectivecontrol.
4. Thisfunctionisusedtoinhibitpowerconsumptionoftheoperating.Donotuseitforminimizethe
capacityofcurrentandthevoltageforthepowercircuit,powersupplywiring,GFCI,transformer,etc.It
maycauseactuationoftheinterrupterandequipmentfault.
5. Powerconsumptiondependsonconnectedoutdoorunit.
without
Power Saving Setting
Maximum Capacity Operation
in Power Saving Set Value Range
Morning NightDaytime
Operation Time
Power
Consumption
Power Saving
Set Value
It can be selected from
100%, 90%, 80%, 70%,
60%, 50%, and 40%
of reference power consumption.
“Moderate Control” Function
Themoderatecontrolmoderatetheairconditioningcapacitynottoexceedthevalueofthepower
savingsetting.
“Peak Cut Control” Function
Thepeakcutcontrolreducesthepowerconsumptionrangewhenitexceedsthevalueofthepower
savingsetting.
without
Moderate Control Setting
Moderate Control Setting
Operation Time
Power
Consumption
NOTES:
1. Themoderatecontrolsettingvaluecanbesetfrom40%to100%ofregularcapacitybyevery10%.
2. Thesettingvalueisjustacriterion.Itmightbedifferentaccordingtotheactualserviceconditionand
operatingcondition.