SM-18001-rev.1
5-39
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(2) RotationControlFunction
TherotationcontrolswitchesmultipleindoorunitoperatingmodetoFANmode(Thermo-OFF)inorder
onebyone.
Fan
Operation*
1
Fan
Operation*
1
Fan
Operation*
1
Cooling Operation
Cooling Operation
Cooling
Operation
Cooling
Operation
Time
Indoor Unit 1
Indoor Unit 2
Indoor Unit 3
Order of Fan
Operation
1
Order of Fan
Operation
2
Order of Fan
Operation
In3
The indoor unit fan
operation is
performed in rotation by
indoor unit address Nos.
NOTES:
1.Thefanmodetimecanbeselectedintheintervalofthreeminutes,veminutesandtenminutes.
2.Itispossibletochangetherotationassignednumberaccordingtotheminimumdifferentialbetween
thesettingtemperatureandindoortemperature.
(3) IntermittentControlFunction
TheintermittentcontrolrepeatsCooling/HeatingandFan(Thermo-OFF)modeinxedintervals.
30 Minutes 30 Minutes
Cooling Operation
20 Minutes
Cooling Operation
20 Minutes
Fan Operation
10 Minutes
Fan Operation
10 Minutes
Cooling Operation
17 Minutes
Cooling Operation
17 Minutes
Fan Operation
13 Minutes
Fan Operation
13 Minutes
Cooling Operation
15 Minutes
Cooling Operation
15 Minutes
Fan Operation
15 Minutes
Fan Operation
15 Minutes
Time
SAV: LOW
SAV: ME
D
SAV: HIGH
NOTE:
Thefanmodeisrepeatedintheintervalofveminutes(SAV:LOW),tenminutes(SAV:MED)andfteen
minutes(SAV:HIGH)duringheatingoperation.