EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Operation Lock (60) to (63)
Fouroperationlockfunctionsareavailableasshownbelow.
Thesefunctionsareutilizedtorestricteachswitchoperationfromthewiredcontroller.
Whenthesefunctionsarevalid,modicationofeachfunctionisprohibited.
Alloperationlockfunctionsarevalid(“01”setting)beforeshipment.
Eachswitchoperationbecomesunavailablebypressing“
”and“Back/Help”(return)buttons
simultaneouslyformorethan3secondswhenthesefunctionsaresetas“01”.Theindication“ ”(operation
lockindicator)isindicatedonthewiredcontroller.If“ ”and“Back/Help”(return)switchesarepressed
simultaneouslyformorethan3secondsduring“ ”(operationlockindicator)isindicated,“ ” indication
isturnedOFFandeachswitchoperationisavailable.Thesefunctionsaretorestricttheoperationsof
thewiredcontrolleronly.Ifoperationispreformedfromthecentralizedcontroller,thecommandfromthe
centralizedcontrollerisgivenpriority.
(60) Lock Function for Operation Mode Selection (F8)
(61) Lock Function for Temperature Setting (F9)
(62) Lock Function for Fan Speed Selection (FA)
(63) Lock Function for Swing Louver Operation (Fb)
(58) Automatic Reset Temperature for Heating (F6)
ThisfunctionisutilizedtosettheautomaticresettemperatureforHEAToperation.
Thesettingconditionsandtheautomaticresettemperatureforheatingareasfollows:
(59) Operation Stoppage Prevention by Wired Controller Operational Error (F7)
Thisfunctionisutilizedtopreventtheaccidentaloperationalstoppagecausedbyinadvertently
pressing“
”(ON/OFF)onthewiredcontroller.Whenthisfunctionisvalid,theoperationisstoppedby
pressing“ ”(ON/OFF)buttononthewiredcontrollerformorethan3seconds.However,theenabling
methodisnotchanged.
SettingCondition SettingTemperatureforAutomaticReset
62(17) 62
o
F(17
o
C)
64(18) 64
o
F(18
o
C)
66(19) 66
o
F(19
o
C)
68(20) 68
o
F(20
o
C)
70(21) 70
o
F(21
o
C)(Factory-Setting)
72(22) 72
o
F(22
o
C)
74(23) 74
o
F(23
o
C)
76(24) 76
o
F(24
o
C)
77(25) 77
o
F(25
o
C)
78(26) 78
o
F(26
o
C)
80(27) 80
o
F(27
o
C)
82(28) 82
o
F(28
o
C)
84(29) 84
o
F(29
o
C)
86(30) 86
o
F(30
o
C)