vii
Electrical Precautions
Takethefollowingprecautionstoreducetheriskofelectricshock,reor
explosionresultinginseriousinjuryordeath.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Performallelectricalworkinstrictaccordancewiththismanualandalltherelevantregulatory
standards.
Beforeservicing,openandtagalldisconnectswitches.Neverassumeelectricalpoweris
disconnected.Checkwithmeterandequipment.
Onlyuseelectricalprotectionequipmentandtoolssuitedforthisinstallation.
Insulateawiredcontrolleragainstmoistureandtemperatureextremes.
Usespeciedcablesbetweenunits.
Thenewairconditionermaynotfunctionnormallyinthefollowinginstances:
Ifelectricalpowerforthenewairconditionerissuppliedfromthesametransformerasthe
externalequipment*referredtobelow.
Ifthepowersupplycablesforthisexternalequipment*andthenewairconditionerunitare
locatedincloseproximitytoeachother.
externalequipment*:(Example):Alift,containercrane,rectierforelectricrailway,inverter
powerdevice,arcfurnace,electricfurnace,large-sizedinductionmotorandlarge-sized
switch.
Regardingthecasesmentionedabove,surgevoltagemaybeinductedintothepowersupply
cablesforthepackagedairconditionerduetoarapidchangeinpowerconsumptionofthedevice
andanactivationofaswitch.
Checkeldregulationsandstandardsbeforeperformingelectricalworkinordertoprotectthe
powersupplyforthenewairconditionerunit.
CommunicationcablingshallbeaminimumofAWG18(0.82mm
2
),2-Conductor,StrandedCopper.
ShieldedcablemustbeconsideredforapplicationsandroutinginareasofhighEMIandother
sourcesofpotentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.
Whenshieldedcablingisapplied,properbondingandterminationofthecableshieldisrequired
asperJohnsonControlsguidelines.Plenumandriserratingsforcommunicationcablesmustbe
consideredperapplicationandlocalcoderequirements.
Thepolarityoftheinputterminalsisimportant,sobesuretomatchthepolaritywhenusingcontacts
thathavepolarity.
Useanexclusivepowersupplyfortheairconditionerattheunit’sratedvoltage.
Highlydangerouselectricalvoltagesmaybeusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Beforeinstallingthecontrollerorremotedevices,ensurethattheindoorandoutdoorunitoperation
hasbeenstopped.Further,besuretowaitatleastveminutesbeforeturningoffthemainpower
switchtotheindoororoutdoorunits.Otherwise,waterleakageorelectricalbreakdownmayresult.
DonotopentheservicecoveroraccesspaneltotheindoororoutdoorunitswithoutturningOFFthe
mainpowersupply.Beforeconnectingorservicingthecontrollerorcablestoindoororoutdoorunits,
openandtagalldisconnectswitches.Neverassumeelectricalpowerisdisconnected.Checkwitha
meterandequipment.
ThisequipmentcanbeinstalledwithaGroundFaultCircuitBreaker(GFCI),whichisarecognized
measureforaddedprotectiontoaproperlygroundedunit.Installappropriatesizedbreakers/fuses
/overcurrentprotectionswitches,andwiringinaccordancewithlocal,stateandNECcodesand
requirements.Theequipmentinstallerisresponsibleforunderstandingandabidingbyapplicable
codesandrequirements.