EasyManuals Logo

York LX series Installation Manual

York LX series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
34
Dual Capacity Models
First Stage Operation
Entering
Water Temp
°F
Water Flow
gpm/ton
Cooling -- No Hot Water Generation
Suction Pressure
psig
Discharge Pressure
psig
Superheat Subcooling
Water Temp
Rise °F
Air Temp Drop
°F DB
30
1.5 111 - 125 140 - 155
32 - 43 5 - 13
14 - 19 17 - 25
3.0 108 - 122 135 - 148 5 - 10 17 - 25
50
1.5 138 - 153 210 - 240
12 - 18 5 - 12
15 - 20 17 - 25
3.0 135 - 150 185 - 215 6 - 11 17 - 25
70
1.5 142 - 157 270 - 300
7 - 13 5 - 12
15 - 20 17 - 25
3.0 140 - 155 250 - 280 6 - 11 17 - 25
90
1.5 142 - 163 350 - 380
6 - 12 5 - 12
13 - 19 17 - 25
3.0 144 - 158 330 - 360 5 - 10 17 - 25
110
1.5 154 - 169 435 - 465
6 - 12 5 - 12
13 - 19 17 - 25
3.0 153 - 167 420 - 450 5 - 10 17 - 25
Entering
Water Temp
°F
Water Flow
gpm/ton
Heating -- No Hot Water Generation
Suction Pressure
psig
Discharge Pressure
psig
Superheat Subcooling
Water Temp
Drop °F
Air Temp Rise
°F DB
30
1.5 77 - 87 275 - 305
6 - 12 8 - 15
5 - 9 15 - 25
3.0 81 - 91 280 - 310 2.5 - 6 16 - 26
50
1.5 105 - 120 295 - 325
7 - 13 8 - 15
5 - 9 18 - 28
3.0 110 - 125 305 - 335 3 - 7 20 - 30
70
1.5 140 - 155 330 - 360
8 - 14 8 - 15
6 - 10 24 - 36
3.0 145 - 160 335 - 365 5 - 9 26 - 38
90
1.5 180 - 195 345 - 385
12 - 18 6 - 13
9 - 14 28 - 40
3.0 185 - 200 355 - 395 7 - 11 30 - 42
110
1.5
3.0
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Second Stage Operation
Entering
Water Temp
°F
Water Flow
gpm/ton
Cooling -- No Hot Water Generation
Suction Pressure
psig
Discharge Pressure
psig
Superheat Subcooling
Water Temp
Rise °F
Air Temp Drop
°F DB
30
1.5 103 - 118 162 - 182
35 - 45 8 - 15
17 - 23 17 - 25
3.0 100 - 115 142 - 162 8 - 11 17 - 25
50
1.5 124 - 138 220 - 250
20 - 26 8 - 15
18 - 24 17 - 25
3.0 122 - 136 195 - 225 9 - 12 17 - 25
70
1.5 133 - 147 290 - 320
9 - 15 8 - 15
18 - 24 17 - 25
3.0 130 - 145 260 - 290 9 - 12 17 - 25
90
1.5 137 - 148 370 - 400
6 - 12 8 - 15
18 - 24 17 - 25
3.0 135 - 146 340 - 375 9 - 12 17 - 25
110
1.5 145 - 158 445 - 485
6 - 12 8 - 15
17 - 23 17 - 25
3.0 143 - 156 430 - 470 8 - 11 17 - 25
Entering
Water Temp
°F
Water Flow
gpm/ton
Heating -- No Hot Water Generation
Suction Pressure
psig
Discharge Pressure
psig
Superheat Subcooling
Water Temp
Drop °F
Air Temp Rise
°F DB
30
1.5 68 - 82 290 - 320
6 - 12 13 - 19
5 - 10 15 - 28
3.0 72- 87 300 - 330 3 - 7 17 - 30
50
1.5 100 - 115 315 - 355
7 - 13 13 - 19
7 - 11 20 - 32
3.0 105 - 120 325 - 365 4 - 8 22 - 35
70
1.5 131 - 146 340 - 380
8 - 14 12 - 18
9 - 14 25 - 37
3.0 136 - 151 350 - 390 6 - 10 27 - 40
90
1.5 165 - 185 385 - 425
13 - 20 9 - 16
10 - 16 30 - 46
3.0 170 - 190 395 - 435 8 - 13 32 - 48
110
1.5
3.0
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. 7/24/2014
Heating performance based on entering air temperature of 70º F DB.
036 Operating Parameters
LX SERIES INSTALLATION MANUAL

Other manuals for York LX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York LX series and is the answer not in the manual?

York LX series Specifications

General IconGeneral
RefrigerantR-410A
SeriesLX
Cooling Capacity1.5 to 5 tons
Warranty10-year limited warranty
Sound LevelAs low as 72 dBA (depending on model)

Related product manuals