YORK INTERNATIONAL
FORM 160.73-O2 (605)
10
 2. To start the chiller, press the COM PRES SOR 
START  switch. This switch will au to mat i cal ly 
spring return to the RUN position. (If the unit was 
pre vi ous ly  started,  press  the  STOP/RE SET  side 
of the COMPRESSOR switch and then press the 
START side of the switch to start the chiller.) When 
the start switch is energized, the Control Center is 
placed in an operating mode and any malfunction 
will be not ed by messages on a graphic display. 
Any malfunctions which oc cur dur ing 
STOP/RE SET are also displayed.
When the chiller is shut down, the prerotation vanes will 
close au to mat i cal ly  to  prevent  load ing the com pres sor 
on start-up. 
When the chiller starts to op er ate,  the  fol low ing  au-
 to mat ic sequences are initiated: (Refer to Fig. 4 & 5, 
“Chill er  Start ing  &  Shutdown  Se quence  Chart”.)
 1. The OptiView Control Center display mes sage will 
read SYSTEM PRELUBE for the fi rst 50 sec onds 
of the start ing sequence.
  2. The oil pump will start to circulate oil for a 50 sec ond 
pre-run to establish oil fl ow and ad e quate  lu bri ca tion 
to all bearings, gears, and rotating sur fac es  within 
the compressor.
   The high and low oil pressure transducers (OP) and 
the oil temperature sensor (RT3) will sense any mal-
function in the lubrication system.
 3. The anti-recycle timer (non-VSD Chillers only) 
software function will op er ate  af ter  the  50  seconds 
of pre-run time. At this time, the timer will be initi-
ated and will run for 30 min utes after the compressor 
starts. If the chiller shuts down during this period of 
time, it cannot be started until the timer com pletes 
the 30 minute cy cle.
 4. The chilled liquid pump contacts will close, start-
 ing the chilled liquid pump, to allow liquid fl ow 
through the evaporator when the COMPRESSOR 
start switch is energized.
 5. After the fi rst 50 seconds of operation, the com-
 pres sor  will  start.
 6. For display messages and information per tain ing  to 
the op er a tion  of  the  OptiView™  Con trol  Cen ter,  re fer 
to Form 160.54-O1.
FIG. 4 –  CHILLER STARTING SEQUENCE & SHUT DOWN SEQUENCE
  (EM STARTER & SOLID STATE STARTER)
LD04040
**   NOT FOR ALL SHUTDOWNS. REFER TO “DISPLAY MES-
 SAG ES” SECTION OF THIS MANUAL.