EasyManua.ls Logo

York R123 - Page 117

York R123
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM 160.55-O1 (604)
117
YORK INTERNATIONAL
Phase C Current = 190 A
Phase A Temperature = 88 ~F
Phase B Temperature = 89 ~F
Phase C Temperature = 75 ~F
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
-------------------------------------------------------------------------
Motor Run = On
% Full Load Amps = 94 %
Pre-Rotation Vanes Position = 75 %
Full Load Amps = 402 A
Precharge Relay Output = Off
Trigger SCR Output = On
Water Pump Output = On
KW Hours = 14528 KWH
Input Power = 150 KW
Output Frequency = 60 Hz
Output Voltage = 800 V
DC Bus Voltage = 600 V
DC Inverter Link Current = 300 A
Phase A Output Current = 195 A
Phase B Output Current = 198 A
Phase C Output Current = 193 A
Internal Ambient Temperature = 88 ~F
Converter Heatsink Temperature = 102 ~F
Phase A Heatsink Temperature = 93 ~F
Phase B Heatsink Temperature = 99 ~F
Phase C Heatsink Temperature = 97 ~F
[Skip the following section if Motor Type is not VSD,
or Filter
is not present]
Harmonic Filter Data
-------------------------------------------------------------------------
Precharge Contactor = Off
Supply Contactor = On
Operating Mode = Running
Phase Rotation = ABC
Total Supply KVA = 148 KVA
Total Power Factor = 0.97
DC Bus Voltage = 608 V
Heatsink Temperature = 102 ~F
Voltage Peak N-L1 = 200 V
Voltage Peak N-L2 = 200 V
Voltage Peak N-L3 = 200 V
L1-L2 RMS Voltage = 215 V
L2-L3 RMS Voltage = 215 V
L3-L1 RMS Voltage = 215 V
L1 RMS Filter Current = 150 A
L2 RMS Filter Current = 150 A
L3 RMS Filter Current = 150 A
L1 RMS Supply Current = 152 A
L2 RMS Supply Current = 152 A
L3 RMS Supply Current = 152 A
L1 Voltage Total Harmonic Distortion = 1.5 %
FIG. 44 – CONTINUED