YORK INTERNATIONAL
118
FORM 160.55-O1 (604)
FIG. 45 – SAMPLE PRINTOUT (SETPOINT REPORT)
YORK SETPOINTS
CHILLER ID 0
-------------------------------------------------------------------------
© 1997 - 1999 YORK INTERNATIONAL COR PO -
RA TION
Mon 21 jun 1999 1:27 :39 PM
Software Versions
-------------------------------------------------------------------------
Controls = C.MLM.02.03.102
BIOS = C.MLM.00.03
Kernel = 0.18
GUI = 0.25
SIO = 0.21
GPIC = 0.03
Ext I/O [Skip if Hot Gas Disabled] = 19962021101
VSD [Skip if Motor Type is not VSD] = C.VSD.01.14
SSS [Skip if Motor Type is not Serial SSS] =
C.SSS.01.01
System Information
-------------------------------------------------------------------------
System Language = English
Data Display Mode = English
Control Source = Local
Remote Analog Input Range = 0 10 Volts
Clock = Enabled
Jumper Settings
-------------------------------------------------------------------------
Pre-Run = Standard
Coastdown = Standard
Chilled Liquid Pump Operation = Standard
Refrigerant Selection = R11
Anti-Recycle = Enabled
Power Failure Restart = Auto
Liquid Type = Water
Motor Type = LCSSS
Printer Setup
-------------------------------------------------------------------------
Automatic Printer Logging = Disabled
Log Start Time = 12:00 am
Output Interval = 60 Min
Printer Type = Okidata
Baud = 9600 Baud
Data Bits = 8 Bits
Parity = None
Stop Bits = 1 Bit
COM 2 Setup
-------------------------------------------------------------------------
Baud = 19200 Baud
Data Bits = 8 Bits
Parity = Odd
Stop Bits = 1 Bit
Evaporator
-------------------------------------------------------------------------
Printers
Leaving Chilled Local Setpoint = 45.0 ~F
Leaving Chilled ISN Setpoint = 45.0 ~F
Leaving Chilled Modem Setpoint = 45.0 ~F
Leaving Chilled Analog Setpoint = 45.0 ~F
Leaving Chilled Digital Setpoint = 45.0 ~F
Remote Range = 10.0 ~F
Sensitivity = Normal
Restart Offset = 0.0 ~F
Restart Setpoint = 45.0 ~F
Shutdown Offset = 4.0 ~F
Shutdown Setpoint = 41.0 ~F
Brine Low Evaporator Cutout = 5.0 Psia
Smart Freeze = Off
Refrigerant = Disabled
Condenser
-------------------------------------------------------------------------
High Pressure Warning Threshold = 28.8 Psia
Drop Leg = Disabled
[Skip the following section if Hot Gas Bypass is not
enabled]
Hot Gas
-------------------------------------------------------------------------
Hot Gas = Disabled
Hold Period = 30 Min
Close Percentage = 5 %
Minimum Load = 1 ~F
Maximum Open = 80 %
Surge
-------------------------------------------------------------------------
Surge Sensitivity = 0.3
Shutdown = Enabled
Extended Run = Disabled
Count Limit = 15
Count Window = 5 Min
[Skip the following section if Liquid Level is not
enabled]
Refrigerant Level Control
-------------------------------------------------------------------------
Level Control = On
Setpoint = 50 %
Period = 3.5 Sec
Proportion Limit Open = 15 %
Proportion Limit Close = 45 %
Rate Limit Open = 10 %
Rate Limit Close = 10 %
Purge Control
-------------------------------------------------------------------------
Hi Ef ciency = Off
Maximum Purges / Hour = 20
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
-------------------------------------------------------------------------
Local Motor Current Limit = 100 %
Remote ISN Current Limit = 100 %
Remote Analog Current Limit = 100 %
Remote Digital Current Limit = 100 %