JOHNSON CONTROLS
FORM 201.23-EG2 (713)
15
MODEL:YCIV0770S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 46.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 689.5 170.6 3.7 676.6 196.8 3.2 662.1 226.0 2.8 629.2 248.2 2.4 564.5 248.2 2.1 530.0 233.3 2.1
6.0 709.0 171.7 3.8 695.5 197.6 3.3 680.0 226.6 2.8 644.2 248.0 2.5 569.7 242.9 2.2 536.2 228.8 2.2
7.0 728.8 173.0 3.9 714.8 198.5 3.4 697.4 226.7 2.9 659.6 247.8 2.5 576.2 238.0 2.3 542.0 223.9 2.3
8.0 749.1 174.4 4.0 734.4 199.5 3.4 715.2 226.8 3.0 675.3 247.4 2.6 582.3 232.8 2.4 547.6 219.0 2.3
9.0 769.7 176.1 4.0 754.5 200.6 3.5 733.3 227.1 3.0 691.2 247.0 2.6 588.4 227.7 2.4 553.1 214.3 2.4
10.0 790.7 178.1 4.1 774.9 202.0 3.6 751.7 227.4 3.1 707.2 246.7 2.7 594.3 222.6 2.5 558.1 209.8 2.5
11.0 812.1 180.2 4.2 795.7 203.6 3.6 770.3 227.8 3.2 723.6 246.3 2.8 599.9 217.8 2.6 563.0 205.4 2.6
12.0 834.0 182.6 4.2 816.9 205.3 3.7 789.3 228.2 3.2 740.2 245.9 2.8 605.2 213.2 2.7 567.7 200.9 2.6
13.0 856.2 185.1 4.3 838.5 207.2 3.8 808.6 228.9 3.3 757.1 245.6 2.9 610.1 208.7 2.7 572.5 196.6 2.7
MODEL:YCIV0840S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 46.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 748.4 182.6 3.8 735.1 208.5 3.3 720.1 236.9 2.8 690.4 263.0 2.5 640.3 275.7 2.2 630.5 278.0 2.1
6.0 769.6 184.0 3.8 755.7 209.7 3.3 739.9 238.2 2.9 707.1 263.1 2.5 655.5 276.0 2.2 645.2 278.3 2.2
7.0 791.1 185.5 3.9 776.7 211.0 3.4 760.1 239.6 3.0 724.0 263.2 2.6 671.0 276.2 2.3 660.4 278.6 2.2
8.0 813.1 187.2 4.0 798.1 212.4 3.5 780.9 241.0 3.0 741.2 263.3 2.7 686.8 276.3 2.3 676.0 278.7 2.3
9.0 835.5 189.0 4.1 819.9 214.1 3.6 802.0 242.4 3.1 758.8 263.3 2.7 702.9 276.4 2.4 690.9 278.2 2.3
10.0 858.4 190.9 4.1 842.2 215.7 3.6 823.6 244.0 3.2 776.3 263.4 2.8 719.2 276.5 2.5 697.1 272.2 2.4
11.0 881.7 193.0 4.2 864.9 217.5 3.7 845.6 245.6 3.2 794.4 263.5 2.8 735.9 276.4 2.5 703.5 266.0 2.5
12.0 905.3 195.2 4.3 888.1 219.4 3.8 867.9 247.4 3.3 812.7 263.6 2.9 752.5 276.2 2.6 710.1 259.7 2.6
13.0 929.1 197.6 4.3 911.5 221.4 3.8 890.8 249.3 3.4 831.3 263.7 3.0 759.3 269.5 2.7 716.0 253.0 2.7
MODEL:YCIV0920S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 46.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 821.2 201.2 3.7 807.2 229.1 3.3 791.2 259.7 2.8 762.5 289.7 2.5 716.5 309.3 2.2 707.4 313.0 2.1
6.0 844.2 202.8 3.8 829.7 230.5 3.3 812.9 261.2 2.9 781.4 290.3 2.5 733.9 310.0 2.2 724.3 313.8 2.2
7.0 867.7 204.5 3.9 852.5 232.1 3.4 834.9 262.9 3.0 800.6 290.9 2.6 751.6 310.7 2.3 740.0 313.3 2.2
8.0 891.5 206.4 4.0 875.8 233.9 3.5 857.5 264.6 3.0 820.1 291.5 2.7 769.8 311.3 2.3 747.8 307.2 2.3
9.0 915.8 208.4 4.0 899.5 235.7 3.5 880.5 266.3 3.1 839.9 292.1 2.7 788.2 311.9 2.4 755.3 300.7 2.4
10.0 940.5 210.4 4.1 923.7 237.6 3.6 904.0 268.2 3.2 859.8 292.8 2.8 804.7 311.1 2.4 762.4 293.8 2.4
11.0 965.7 212.7 4.2 948.2 239.6 3.7 927.8 270.0 3.2 880.3 293.4 2.8 812.6 304.1 2.5 769.0 286.5 2.5
12.0 991.2 215.1 4.2 973.3 241.7 3.7 952.1 272.1 3.3 901.1 294.0 2.9 820.0 296.6 2.6 775.2 279.1 2.6
13.0 1017.2 217.0 4.3 998.6 243.9 3.8 976.9 274.2 3.3 922.2 294.7 2.9 826.9 289.0 2.7 780.9 272.0 2.7
NOTES:
1. kWo = UnitkWCoolingCapacityOutput
2. kW
i
= CompressorkWInput
3. COP = CoefcientofPerformance(includescondenserfanpower)
4. LCWT = LeavingChilledWaterTemperature
5. Ratingsbasedon0.168l/scoolerwaterperton,and0.018(m
2
–°C)/kW
6.AHRI550/590doesnotprovidecerticationfor50Hzratings.TheuniqueuseoftheYCIVvariablespeeddriveallowscompressoroperationattheoutputspeedregardlessoftheinput
powerfrequency.Thisallowsforcommonunit/heatexchangercongurationsbetween60Hzand50Hzwithcloselymatchingcapacity.