JOHNSON CONTROLS10
FORM 201.23-EG2 (713)
TEMPERATURE AND FLOWS
(SI Units)
Temperatures and Flows
NOTES:
1. Forleavingbrinetemperaturebelow4.4°C(40°F),contactyournearestJohnsonControlsofceforapplicationrequirements.
2. Forleavingwatertemperaturehigherthan15.6°C(60°F),contactthenearestJohnsonControlsofceforapplicationguidelines.
3. Theevaporatorisprotectedagainstfreezingto-28.8°C(-20°F)withanelectricheaterasstandard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(L/S)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
50 HZ
0600(S/P) 4.4 15.6 8.8 42.6 -17.8 51.7
0590(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0650(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0630(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0720(S/P/) 4.4 15.6 10.1 47.3 -17.8 51.7
0700(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0760(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0770(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0800(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0840(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0830(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7